UNITED STATES DISTRICT COURT
FOR THE DISTRICT OF COLUMBIA
ST. PAUL MERCURY INSURANCE
COMPANY, as Subrogee of Gallaudet
University,
Plaintiff,
v.
Civil Action No. 05–2115 (CKK)
CAPITOL SPRINKLER INSPECTION,
INC.
Defendant/Third-Party Plaintiff,
v.
GUEST SERVICES, INC.
Third-Party Defendant.
MEMORANDUM OPINION
(June 15, 2009)
On January 25, 2003, a tee fitting froze and burst in the dry sprinkler system at the
Kellogg Conference Center on the campus of Gallaudet University (“Gallaudet”) in Washington,
D.C., causing significant water damage. This case is about who is legally responsible for the
damage. Plaintiff St. Paul Mercury Insurance Company (“St. Paul”) was Gallaudet’s property
insurer, and has been subrogated for Gallaudet in this litigation. St. Paul filed suit alleging
breach of contract and negligence against Defendant Capitol Sprinkler Inspection, Inc. (“Capitol
Sprinkler”), the company that was contracted to perform semi-annual inspections of the sprinkler
system. Capitol Sprinkler, in turn, filed suit against third-party Defendant Guest Services, Inc.
(“Guest Services”), the building management company at the conference center, also for breach
of contract and negligence.
On September 2, 2008, the Court issued an Order and Memorandum Opinion that held in
abeyance St. Paul’s and Guest Services’s Motions for Summary Judgment against Capitol
Sprinkler. The Court ordered the parties to file supplemental briefing concerning whether
Capitol Sprinkler’s breach of contract and negligence arguments were cognizable in the absence
of any expert testimony proffered by Capitol Sprinkler.1 The Court shall fully incorporate its
September 2, 2008 Memorandum Opinion by reference herein.
After thoroughly reviewing the parties’ original and supplemental submissions to the
Court, relevant case law and statutory authority, and the record of the case as a whole, the Court
finds that Capitol Sprinkler cannot establish the necessary elements of its breach of contract and
negligence arguments in the absence of expert testimony. Accordingly, the Court shall GRANT
St. Paul’s [48] Motion for Partial Summary Judgment as to its breach of contract claim, and
GRANT Guest Services’s [59] Motion for Summary Judgment. Guest Services shall be
dismissed from further proceedings. By separate Order, the Court shall set a Status Hearing to
discuss further proceedings for the two remaining claims in this case – St. Paul’s breach of
contract claim (as to which liability has been established) and St. Paul’s negligence claim (as to
which St. Paul did not move for summary judgment).
1
The arguments advanced by Capitol Sprinkler in support of its (1) defenses to St. Paul’s
breach of contract and negligence claims, (2) claims against Guest Services for breach of contract
and negligence, and (3) opposition to Guest Services’s Motion for Summary Judgment, are
substantially similar. Throughout this Memorandum Opinion, the Court shall refer to Capitol
Sprinkler’s “arguments,” with the understanding that the arguments were made to defend against
St. Paul’s Motion for Summary Judgment and to support its own Motion for Summary Judgment
against Guest Services and St. Paul.
2
II. BACKGROUND
A. Factual Background 2
Gallaudet is the owner of the Kellogg Conference Center (the “Conference Center”) in
Washington, D.C. Pl.’s Stmt. ¶ 1. The Conference Center is a five-story building that houses
meeting rooms, 93 guest rooms, and other areas. Def.’s Stmt. ¶¶ 3, 4. The building has a
sprinkler system that was installed by Capitol Sprinkler either during its construction between
1996-1998 or thereafter. Id. ¶ 2. Portions of the building are restricted (such as the guest rooms)
and are accessible only by using specific key cards. Id. ¶ 9.
On February 11, 2002, Gallaudet contracted with Guest Services to provide operational
and management services for the Conference Center. Id. ¶ 13. Guest Services, in turn,
contracted with Capitol Sprinkler on April 22, 2002, to perform semi-annual inspections of the
sprinkler systems at the Conference Center. Pl.’s Stmt. ¶ 2.
The agreement between Guest Services and Capitol Sprinkler (hereinafter, the
“Inspection Agreement”) obligated Capitol Sprinkler to “open condensation drains on drum drip
connections and drain low points during fall and winter inspection[s].” Id. ¶ 3. Vernon Vane,
Capitol Sprinkler’s supervisor of inspections, confirmed that Capitol Sprinkler’s inspectors were
supposed to drain “drum drips” during inspections in accordance with this provision:
Q: . . . And under that it says “[o]pen compensation drains on drum [drip]
connections and drain low points during fall and winter inspection.” That right?
A: That’s correct.
Q: That is the work that’s supposed to be done by Capitol Sprinkler’s people
2
This section contains facts drawn from the Court’s September 2, 2008 Memorandum
Opinion, which are necessary to provide context for the motions that were held in abeyance.
3
when they are at the job site. Is that correct?
A: That’s correct.
Pl.’s Mot., Ex. D at 49:11 - 49:18 (Depo. Tr. of V. Vane); Pl.’s Stmt. ¶ 6 (same).
On January 9, 2003, Capitol Sprinkler employees Michael Bowlin and Tom Scott
inspected the sprinkler system at the Conference Center. Pl.’s Stmt. ¶¶ 7, 8. Because they
needed access to certain areas of the building that were restricted, the inspectors were
accompanied by an escort who could provide them with such access. Def.’s Stmt. ¶¶ 16; 21.
During the inspection, Mr. Bowlin and Mr. Scott drained all of the drum drips except for the one
that was located above the building’s conference room 5200. Pl.’s Mot., Ex. F at 50:10 - 50:15
(Depo. Tr. of M. Bowlin) (“Q: Now did you drain, you and Mr. Scott, drain all of the drain points
during the January 9, 2003 inspection? A: All but the one in that room. Q: The one above
conference room 5200? A: Correct”). The drum drip above conference room 5200 was the last
one that needed to be drained during the January 9, 2003 inspection. Def.’s Stmt. ¶ 28. Mr.
Bowlin testified that he and Scott were supposed to drain that drum drip. Id. at 50:21 - 50:22
(“Q: Were you supposed to drain that drain? A: Yes”).
According to Mr. Bowlin’s deposition testimony, and not refuted by contradictory
evidence in the record, Mr. Bowlin and Mr. Scott did not drain the drum drip above conference
room 5200 because their escort did not have immediate possession of the key card necessary to
give them access to the room: “We were going to the room and when we got to the room he [the
escort] says, ‘I don’t have a card. I have to go down stairs and get the card for the access.’” Pl.’s
Opp’n, Ex. 7 at 51:22 - 52:3 (Depo Tr. of M. Bowlin). Mr. Bowlin’s testimony is internally
inconsistent as to whether he asked the escort to retrieve the key card. Compare id. at 54:18 -
4
54:21 (“Q: . . . did you ask him to go get the card? A: No, I didn’t ask him to go get the card”)
with id. at 56:6 - 56:14 (“Q: Why didn’t you ask him to go get the card so you could have access
to drain the last drain you had left? A: I asked him to get the card but I don’t remember him
going to get the card. Q: So you don’t remember him saying, ‘I refuse to get the card’ or
anything like that? A: He didn’t refuse to get the card”). Nevertheless, Bowlin testified that he
asked the escort to drain the drum drip himself instead of retrieving the key card:
he just kind of looked at us like, you know, he really didn’t want to [get the key
card] – he would take care of it. He said he would take care of the drum drip, and
I asked him, I said ‘Are you going to take care of this’ – I said, ‘You know what?
I can’t get in the room. Are you going to take care of this drum [drip]?
Id. at 54:11 - 54:17. See also id. at 56:16 - 56:22 (“Q: . . . Did you ask him, since you don’t have
a card, ‘Will you take care of the drum drip?’ A: I asked him if he would take care of the drum
drip. Q: So you made a request? A: I made a request”). Mr. Bowlin indicated that it would have
taken between five to ten minutes to retrieve the key card, or “[h]owever long it takes [] to get to
the elevator, go downstairs to the front desk, or however fast the elevator runs.” Def.’s Opp’n to
Pl.’s Mot., Ex. E at 52:11 - 52:21 (Depo. Tr. of M. Bowlin). Mr. Bowlin and Mr. Scott left the
building and completed an inspection report, indicating that all of the “dry valves [were]
protected from freezing” and “all areas and valves [were] protected from freezing.” Third-Party
Def.’s Stmt. ¶¶ 10, 11; Def.’s Resp. Third-Party Stmt. ¶ 10. No “deficiencies” were noted on the
report, and the report does not indicate that a drum drip had not been drained or that the
inspectors had requested that an escort drain a drum drip. See Third-Party Def.’s Mot., Ex. 5 at 2
(7/9/03 Inspection Report).
The drum drip above conference room 5200 was never drained. Pl.’s Stmt. ¶ 13; Def.’s
Resp. Stmt. ¶ 13. On January 25, 2003, a tee fitting in the sprinkler system froze and burst,
5
allowing water to discharge. Pl.’s Stmt. ¶ 11. It is undisputed that the tee fitting froze and burst
because the drum drip had not been drained during the January 9, 2003 inspection. Pl.’s Stmt. ¶
13.
B. Procedural Background
1. Breach of Contract Claims
St. Paul moved for partial summary judgment on its breach of contract claim based on the
following undisputed facts: (1) Capitol Sprinkler was contractually obligated to drain all drum
drips in the sprinkler system during its January 9, 2003 inspection; (2) Capitol Sprinkler did not
drain one of the drum drips during that inspection; (3) the drum drip that Capitol Sprinkler did
not drain was on the same branch line as the tee fitting which froze and ruptured; and (4) the
rupture of the tee fitting and resulting damage to the Conference Center are the direct result of
Capitol Sprinkler’s failure to perform its express contractual obligations.3 See Pl.’s Mot. at 2. In
its September 2, 2008 Memorandum Opinion, the Court found that entry of partial summary
judgment in favor of St. Paul was appropriate unless Capitol Sprinkler could raise a defense
pursuant to which a jury could find that Capitol Sprinkler’s obligation to perform under the
Inspection Agreement was alleviated. In this regard, Capitol Sprinkler argued that it was relieved
of its obligations under the Inspection Agreement because Guest Services breached the contract
between Capitol Sprinkler and Guest Services. According to Capitol Sprinkler, the acts of Guest
Services were attributable to Gallaudet because Guest Services was Gallaudet’s agent. See
Def.’s Opp’n to Pl.’s Mot. at 8-10; Def’s Reply to Pl.’s Opp’n at 9.
3
St. Paul’s Motion for Partial Summary Judgment was supported by the report of its
expert, Kenneth R. McLauchlan.
6
With respect to this contract-based defense, Capitol Sprinkler argued that the Inspection
Agreement incorporated National Fire Protection Association 25 (“NFPA 25”), a set of standards
concerning the inspection, testing, and maintenance of water-based fire protection systems. See
Def.’s Opp’n to Pl.’s Mot. at 12. Pursuant to NFPA 25, property owners must “provide ready
accessibility to components of water-based fire protection systems that require inspection,
testing, or maintenance.” Def.’s Opp’n, Ex. G-1 § 4.1.1 (NFPA 25, 2002 Edition). NFPA 25
provides that this and other obligations may be transferred by a property owner to others where,
as here, the owner is not the occupant of the building. Id. §§ 4.1.2.3, 4.1.2.4 (“the property
owner shall be permitted to pass on the authority for inspecting, testing, and maintaining the fire
protection systems to the occupant, management firm, or managing individual . . . [who] shall
comply with the requirements identified for the owner or occupant throughout this standard.).
According to Capitol Sprinkler, Guest Services breached the Inspection Agreement by
“failing to provide Capitol Sprinkler with access to all components of the subject sprinkler
system.” Def.’s Opp’n to Pl.’s Mot. at 14. Assuming a jury would find that NFPA 25 was
incorporated as a term in the Inspection Agreement, Capitol Sprinkler argues that Guest Services
breached the “ready accessibility” standard set forth in section 4.1.1, see Def.’s Opp’n, Ex. G-1 §
4.1.1 (NFPA 25, 2002 Edition), because Capitol Sprinkler could not access the drum drip above
conference room 5200.4
4
In its Supplemental Brief, Guest Services argues that the Inspection Agreement did not
include NFPA 25 as one of its terms because the agreement instead referenced NFPA 13-A. See
Third-Party Suppl. Br. at 4-5. Guest Services’s inclusion of this argument in its Supplemental
Brief is baffling because the Court already held that “a genuine [and disputed] issue of material
fact exists as to whether NFPA 25 was incorporated as a term into the Inspection Agreement
despite its reference to NFPA 13-A.” Mem. Op. at 29 (Sept. 2, 2008).
7
In its September 2, 2008 Memorandum Opinion, the Court explained that Capitol
Sprinkler would have to show what duty was created by the “ready accessibility” standard in
order to show that such a standard had been breached. The Court also explained that the parties
presented two very different interpretations of what the phrase “ready accessability” required.
According to Capitol Sprinkler, that phrase required a sort of instantaneous access to all sprinkler
components. See, e.g., Def.’s Reply to Pl.’s Opp’n at 4 (“an inspector must be able to have
access to the component locked behind any such door or panel . . . Guest Services did not unlock
the door to allow the inspector to enter and access the drum drip, and therefore, breached the
contract”). According to St. Paul and Guest Services, that phrase required that an owner not
place immobile objects in front of sprinkler components. See Pl.’s Opp’n at 12-13; Third-Party
Def.’s Reply at 4. St. Paul and Guest Services both cited to the NFPA 25 Appendix, titled
“Explanatory Material,” which appeared to support their interpretation of the “ready
accessibility” language:
[t]he components are not required to be open or exposed. Doors, removable
panels, or valve pits may be permitted to satisfy the need for accessibility. Such
equipment should not be obstructed by features such as walls, ducts, columns,
direct burial, or stock storage.
App’x. A-1-4.1.
The Court found that Capitol Sprinkler would likely require expert testimony to establish
the meaning of the “ready accessibility” standard in NFPA 25, but noted that the parties had
devoted little attention to the absence of an expert opinion in the record. Because the Court was
unwilling to rule on the dispositive issue of whether Capitol Sprinkler could support its contract-
based claim in the absence of an expert opinion, it ordered supplemental briefing on the
following issue: “whether Capitol Sprinkler can establish, without an expert opinion, what duty
8
the ‘ready accessibility’ standard of NFPA 25 imposed on Guest Services and/or Gallaudet.”
Order at 2 (Sept. 2, 2008).
2. Negligence Claims
Capitol Sprinkler filed Motions for Summary Judgment against St. Paul and Guest
Services arguing that it should be relieved of liability based on the negligent acts of Gallaudet (as
the subrogee of St. Paul) and Guest Services. If Gallaudet were found negligent, St. Paul would
be unable to recover as the subrogee. In this regard, Capitol Sprinkler raised three discernable
negligence-based arguments. First, it argued that Guest Services was Gallaudet’s agent, and that
Guest Services was negligent when it “thwarted” Capitol Sprinkler’s inspection of the sprinkler
system:
the property owner had a duty to maintain the building’s sprinkler system; the
owner contracted with a property management agent to perform that maintenance;
the property management agent hired Capitol Sprinkler to perform inspections and
maintenance; the property management agent thwarted Capitol Sprinkler’s ability
to perform and agreed to reassume the duty to inspect and maintain; and, the
property management agent failed in its duty and caused the damages in this case
. . . [thus] plaintiff is contributorily negligent.
Def.’s Reply to Pl.’s Opp’n at 8. Second, Capitol Sprinkler argued that Gallaudet, as the owner
of the conference center, had a duty under NFPA 25 to inspect the conference center’s sprinkler
system, and that this obligation was not transferrable. See Def.’s Reply to Pl.’s Opp’n at 9-10.
This argument was grounded in section 1-4.2 of NFPA 25, which provides that
[the] responsibility for properly maintaining a water-based fire protection system
shall be that of the owner(s) of the property . . . [but] [w]here the owner is not the
occupant, the owner shall be permitted to pass on the authority for inspecting,
testing, and maintaining the fire protection systems to the occupant, management
firm . . . .
Pl.’s Opp’n, Ex. 4 at 1 (NFPA 25 1-4.2 (1998 Ed.)). According to Capitol Sprinkler, this
9
provision allowed Gallaudet to transfer the authority to maintain the sprinkler system, but not the
responsibility for its maintenance. Def.’s Reply to Pl.’s Opp’n at 9-10. Third, Capitol Sprinkler
argued that Guest Services was negligent because NFPA 25 imposes an obligation on the
building management agent to either provide the requisite access to the inspectors to maintain the
sprinkler system, or to undertake the maintenance itself; because Capitol Sprinkler alleged that it
was denied access to the drum drip above conference room 5200, it argued that Guest Services
breached its duty to drain the drum drip. Def.’s Mot. against Third-Party Def. at 17-18.
After reviewing the parties’ briefing associated with these arguments, the Court again
found that there were questions yet to be resolved concerning whether Capitol Sprinkler could
prove these negligence-based arguments without the benefit of expert testimony. Accordingly,
the Court ordered the following supplemental briefing in connection with Capitol Sprinkler’s
negligence claims:
whether Capitol Sprinkler can establish, without an expert opinion, that NFPA 25
establishes the requisite standard of care as to these parties, and whether Capitol
Sprinkler can prove the following elements corresponding to its three negligence-
based defenses: (1) the standard of care (i.e., what specific duty was required)
that was breached when Guest Services allegedly ‘thwarted’ Capitol Sprinkler’s
inspection, i.e., whether it was based on a breach of the ‘ready accessibility’
standard, and the meaning of ‘thwarted’ in this context, (2) the basis for
Gallaudet’s allegedly non-transferrable duty to inspect its sprinkler systems (i.e.,
that NFPA 25 incorporates the distinction between ‘authority’ and ‘responsibility’
that Capitol Sprinkler identifies), and that Gallaudet’s transfer or attempted
transfer of this duty caused, in whole or in part, the damages in this case, and (3)
the standard of care (i.e., what specific duty was required) that was breached when
Guest Services allegedly denied Capitol Sprinkler access to sprinkler system
components, and the standard of care (i.e., what specific duty was required) that
was breached by not performing the maintenance itself.
Order at 2 (Sept. 2, 2008).
10
III. DISCUSSION
Although the Court’s Order requested supplemental briefing that addressed the very
specific issues identified above, Capitol Sprinkler decided to ignore the Order and submit a
Supplemental Brief consisting largely of various case descriptions where courts found that expert
testimony was unnecessary. The Supplemental Brief makes no attempt to address each of the
issues identified in the Order and otherwise fails to provide any guidance as to which issues
Capitol Sprinkler intended to address. Notwithstanding these deficiencies (or perhaps consistent
with them), the Court finds it readily apparent that Capitol Sprinkler cannot prevail on its breach
of contract and negligence claims against Guest Services in the absence of expert testimony.
Similarly, Capitol Sprinkler cannot prevail on its breach of contract and negligence defenses
against St. Paul, as presented in Capitol Sprinkler’s Motion for Summary Judgment against St.
Paul, because without expert testimony, Capitol Sprinkler cannot establish negligence as to
Gallaudet (the subrogee of St. Paul).
A. Breach of Contract
It is well established in the District of Columbia that “‘[a] plaintiff must put on expert
testimony to establish what the standard of care is if the subject in question is so distinctly related
to some science, profession or occupation as to be beyond the ken of the average layperson.’”
District of Columbia v. Arnold & Porter, 756 A.2d 427, 433 (D.C. 2000) (quoting Messina v.
District of Columbia, 663 A.2d 535, 538 (D.C. 1995)). Conversely, “‘no expert testimony is
needed if the subject matter is within the realm of common knowledge and everyday
experience.’” Briggs v. Wash. Metro. Area Trans. Auth., 481 F.3d 839, 845 (D.C. Cir. 2007)
(quoting Hill v. Meto. African Methodist Episcopal Church, 779 A.2d 906, 908 (D.C. 2001)). As
11
the United States Court of Appeals for the District of Columbia Circuit has observed, “[t]he D.C.
Courts of Appeals has required expert testimony in a number of cases that, on first blush, appear
to be within the realm of common knowledge,” such as the maintenance of leaning trees,
application of hair relaxer, or the tightness of handcuffs. Id.
Where the standard of care is “beyond the ken of the average layperson,” the law in the
District of Columbia requires an expert to “clearly articulate and [refer to] a standard of care by
which the defendant’s action can be measured . . . the expert must clearly relate the standard of
care to the practices in fact generally followed by [similarly situated parties] or to some standard
nationally recognized by such [parties].” Nat’l Tel. Coop. Ass’n v. Exxon Mobil Corp., 244 F.3d
153, 154 (D.C. Cir. 2001) (quoting District of Columbia v. Arnold & Porter, 756 A.2d 427, 433
(D.C. 2000)). The expert’s testimony must go beyond establishing the ultimate goal of the
standard and must explain the standard that is generally followed to reach that goal. Id. at 155.
In this case, Capitol Sprinkler asserts that expert testimony is unnecessary because an
average juror would have knowledge about the meaning of “ready accessibility” found in NFPA
25. Specifically, Capitol Sprinkler argues that “the requirement under NFPA that a fire
protection system be made ‘readily accessible’ is not highly technical, and does not create any
dispute as to interpretation.” Def.’s Suppl. Br. at 14. It further argues that “[i]n the context of
this case, the definition of ‘ready accessibility’ is easily understandable” and that the Court
“should not engage in a lengthy examination of the meaning of a term to somehow produce a
contradictory and illogical conclusion.” Id. Finally, Capitol Sprinkler sets forth its vision for
what it believes the “ready accessibility” standard requires:
[Capitol Sprinkler] is not suggesting that the ‘ready accessibility’ standard of
NFPA 25 requires instantaneous access to the fire protection system. Rather, they
12
[sic] are arguing that the meaning of ‘ready accessibility’ can be ascertained by the
average juror in light of the facts surrounding Capitol Sprinkler’s inspection,
particularly that the door was locked and that the Guest Services escort stated
himself [sic] that he would drain the drip drum himself.
Id. at 15. Capitol Sprinkler’s arguments fundamentally misunderstand the law in the District of
Columbia pertaining to expert testimony and are otherwise untenable.
First, the relevant inquiry is not, as Capitol Sprinkler suggests, what the words “ready
accessibility” mean to “the average juror” in some abstract sense. Rather, the appropriate inquiry
is whether the average juror would have knowledge as to what the words “ready accessibility”
mean in the context of the sprinkler inspection standards contained in NFPA 25. This distinction
is critical because expert testimony is required unless “everyday experience makes it clear that
jurors could not reasonably disagree over the care required.” Nat’l Tel. Coop. Ass’n, 244 F.3d at
155. For example, in Briggs v. Washington Metropolitan Area Transit Authority, the D.C.
Circuit considered whether expert testimony was necessary in a case involving a murder at a
metro station in Washington, D.C. See 481 F.3d at 345. The victim’s mother sued the defendant
(“WMATA”) for negligence, claiming that the lighting in the area of the murder was too dim. Id.
at 349. The Court concluded that the plaintiff was required to present expert testimony
concerning the lighting. Id. “While lay persons can certainly distinguish between illumination
and complete darkness, there is nothing to indicate that common knowledge includes a universal
standard of ‘adequate’ lighting within a temporary construction walkway.” Id. at 350. Because a
lighting standard was “not ‘within the realm of common knowledge and everyday experience,’
. . . [the plaintiff] was required to ‘adduce expert testimony . . . to establish the applicable
standard of care.’” Id. (quoting Varner v. District of Columbia, 891 A.2d 260, 265 (D.C. 2006)).
Here, reasonable jurors undoubtedly would have experience with objects that are readily
13
accessible, as that phrase may be independently understood by each juror in his or her everyday
life. It is unlikely, however, that those jurors would have experience with what the phrase “ready
accessibility” means in the context of sprinkler inspections, and specifically, in the context of
NFPA 25. Just as the jurors in Briggs would have an understanding between lightness and
darkness but would nonetheless require expert testimony as to the applicable standard of care
related to the lighting at the metro station, so too the jurors in this case would understand the
concept of accessibility but would nonetheless require testimony as to what standard of care was
required by the “ready accessibility” language in NFPA 25.
None of the cases described by Capitol Sprinkler in its Supplemental Brief support a
different conclusion. For example, in National Railroad Passenger Corporation v. McDavitt, an
employee was injured when a train he was driving derailed in a train yard. 804 A.2d 275 (D.C.
2002). A jury found that railroad personnel were negligent when they failed to monitor the
unauthorized movement of the employee’s train, as they should have been doing. Id. at 280. The
court found that expert testimony was unnecessary given the plaintiff’s theory of liability, which
did not require the assessment of a technical standard:
we have little doubt that expert testimony on the standard of care would have been
required to establish [the employee’s] theories that Amtrak was negligent in
selecting and siting [a train signal], in not taking appropriate measures to protect
against signal malfunctions, and in relying on allegedly outdated technology.
Each of those matters depends heavily upon technical or specialized knowledge
that a lay jury would not be expected to possess . . . . On the other hand, . . . [i]n
the present case, the trial judge who heard and saw what the jury did concluded
that no special expertise was necessary to evaluate whether [the train] personnel
had a duty to respond when unauthorized train movements in the Washington
Terminal coach yard were reported by radio and [other means]. We agree that the
scope of the duty of railroad traffic controllers to attend to notifications of
unauthorized train traffic in the confined space of a rail yard is not so esoteric as
to be beyond the ken of the average layperson.
14
Id. at 285. As is apparent from this discussion, the plaintiff’s theory of liability was not based on
a technical standard that would have required expert testimony, but rather was based on the
common sense proposition that the traffic controllers had a duty, when alerted to unauthorized
train movements, to respond and not ignore such notifications. These facts and this theory of
liability bear no resemblance to the present case, where Capitol Sprinkler’s theory of liability is
that the actions of Gallaudet and/or Guest Services breached a provision of NFPA 25.
Similarly, in Transcontinental Insurance Company v. Simplexgrinnell LP, the plaintiff
alleged that the defendant failed to visually inspect its sprinkler system in an attic space. 2006
U.S. Dist. LEXIS 48654 at *1 (N.D. Ohio Jul. 18, 2006). The defendant argued that its sprinkler
system inspection met all NFPA requirements because “no inspection is required for sprinklers
and piping installed in concealed spaces” and that the defendant’s “inspector testified that the
attic space where the break occurred was inaccessible as there was no flooring.” Id. at *18. The
plaintiff presented expert testimony concerning NFPA 25 and its interpretation, and it is unclear
from the opinion whether Defendant did so as well. For this reason, and unlike the instant case,
there appears to have been no dispute over the applicable standard of care (which was the subject
of testimony by Plaintiff’s expert as to what was required by the NFPA), but rather a question of
fact as to whether the attic had flooring. Id. at *19 (“the Court is presented with genuine issues
of fact whether the attic crawl space was accessible under the NFPA”). Transcontinental
therefore provides no support for Capitol Sprinkler’s argument because the parties in this case do
have a dispute concerning the applicable standard of care. Because the Court finds that the
requirements associated with the “ready accessibility” standard in NFPA 25 are not within the
ken of the average layperson, the Court finds that Capitol Sprinkler must present expert
15
testimony concerning the applicable standard of care.5
Second, contrary to Capitol Sprinkler’s assertion that the “ready accessibility” language
“does not create any dispute as to interpretation,” Def.’s Suppl. Br. at 14, St. Paul and Guest
Services have set forth a plausible argument that the standard relates to whether immobile objects
may be placed in front of sprinkler components – not whether access has been provided to
inspectors within a certain amount of time. This interpretation is supported by reference to the
NFPA 25 explanatory notes for the “ready accessibility” provision:
The components are not required to be open or exposed. Doors, removable
panels, or valve pits can be permitted to satisfy the need for accessibility. Such
equipment should not be obstructed by features such as walls, ducts, columns,
direct burial or stock storage.
NFPA 25 § A.4.1.1. Without expert testimony “offer[ing] credible evidence sufficient to
establish a controlling standard of care,” Briggs, 481 F.3d at 841, Capitol Sprinkler cannot
establish that St. Paul and Guest Services’s interpretation is incorrect, and certainly cannot show
that the language is not subject to reasonable dispute.
Third, Capitol Sprinkler fundamentally misunderstands the role of the jury by making the
following argument:
5
The Court notes that three of the other cases described by Capitol Sprinkler directly
undermine its arguments because the parties in those cases did, in fact, present expert testimony
supporting their arguments. See Graves v. United States, 517 F. Supp. 95 & n.2 (D.D.C. 1981)
(“the Court is persuaded by the testimony of plaintiff’s expert witness who stated that because a
virtually endless supply of steam flows into the converter, the room is a high hazard area within
the meaning of [various] codes” and “Defendant’s own expert conceded that for this reason it did
not qualify as an exit within the meaning of the building and safety regulations”); Washington
Hosp. Ctr. v. Butler, 384 F.2d 331, 336-37 (D.C. Cir. 1967) (“[t]he testimony of experts was not
indispensable to sagacious resolution of the great bulk of the factual questions, and in the few
instances where it was essential it was supplied”); Kull v. Six Flags over Ga. II, 592 S.E.2d 143,
144, 146 (Ga. App. 2003) (referring to the plaintiff’s expert whose testimony was found
unpersuasive).
16
Capitol Sprinkler is not suggesting that the ‘ready accessibility’ standard of NFPA
25 requires instantaneous access to the fire protection system. Rather, they [sic]
are arguing that the meaning of ‘ready accessibility’ can be ascertained by the
average juror in light of the facts surrounding Capitol Sprinkler’s inspection . . . .
Def.’s Suppl. Br. at 15. It is not the role of the jury to speculate about what standard of care is
required, but rather, to determine whether or not the required standard of care has been breached
based on the credible evidence submitted by the parties as to what standard of care is required.
See Tillman v. Wash. Metro. Area Trans. Auth., 695 A.2d 94, 97 (D.C. 1997) (rejecting the
plaintiff’s negligence claim based on police officers’ handcuffing him too tightly because, in the
absence of expert testimony, “[a] jury would have to engage in considerable speculation to find
for [the plaintiff] . . . without any evidence of the applicable standards”). See also Bammerlin v.
Navistar Int’l Transp. Corp., 30 F.3d 898, 900 (7th Cir. 1994) (explaining that the trial judge
made a “serious mistake” by leaving the jury to interpret the meaning of ambiguous motor
vehicle safety standards). Because Capitol Sprinkler has proffered no credible evidence
concerning the meaning of the applicable standard of care required by NFPA 25, the Court agrees
with St. Paul that “[w]ithout expert testimony, a juror would be left to pure speculation to reach
any conclusion regarding the true meaning of ‘ready accessibility’ of equipment under NFPA
25.” Pl.’s Suppl. Br. at 5.
Finally, the Court finds the arguments raised in Capitol Sprinkler’s Supplemental Brief to
be disingenuous. As the Court has discussed in its previous opinions, Capitol Sprinkler failed to
timely take depositions of opposing party witnesses in this case and failed to serve a compliant
Rule 26(a)(2)(B) expert report in violation of the Court’s Scheduling Order. See Mem. Op. at
10-18 (Jun. 1, 2007). Although Capitol Sprinkler subsequently filed a Motion for Leave to
Supplement its Rule 26(a)(2)(B) disclosure (which was filed well after the close of discovery),
17
the Court denied the motion because Capitol Sprinkler failed to demonstrate good cause for its
flagrant disregard of the Court’s Scheduling Order. Id. In seeking to explain why it sought to
present expert testimony, Capitol Sprinkler made the following representation:
It is well accepted in this jurisdiction that expert testimony is required . . . when
the subject matter at issue is so distinctly related to some science, profession,
business or occupation as to be beyond the ken of the average layman.
In this matter, the care due by Capitol [Sprinkler] and Guest Services under their
respective contracts is just the kind of issue on which expert testimony is required.
See Def.’s Reply in Support of Mot. for Leave ¶¶ 5-6 (Feb. 23, 2007) (internal punctuation and
citations omitted). Capitol Sprinkler’s current arguments are therefore in direct conflict with its
previous representations to the Court. Although far from dispositive, the D.C. Court of Appeals
has found similar circumstances to be relevant to the determination of whether expert testimony
was necessary in a given proceeding. See Lowrey v. Glassman, 908 A.2d 30, 36 (D.C. 2006)
(“the very fact that [the plaintiff] designated expert witnesses on [these] subjects . . . belie his
present assertions that he did not need experts to prove his case. Clearly he believed that the
strength of his case depended largely upon the testimony of these witnesses in their particular
areas of expertise”).
Accordingly, the Court finds that Capitol Sprinkler cannot set forth the appropriate
standard of care required by NFPA 25 in the absence of expert testimony, and as a result, cannot
prevail on its arguments that Gallaudet (the subrogee of St. Paul) and/or Guest Services breached
a “ready accessibility” obligation in the Inspection Agreement. The Court shall therefore grant
St. Paul’s Motion for Partial Summary Judgment and find that liability has been established as to
St. Paul’s breach of contract claim against Capitol Sprinkler, and shall grant Guest Services’s
Motion for Summary Judgment as to Capitol Sprinkler’s breach of contract claim against Guest
18
Services.
B. Negligence
The Court’s analysis in the foregoing section is equally applicable to Capitol Sprinkler’s
three negligence arguments: (1) that Guest Services ‘thwarted’ Capitol Sprinkler’s inspection,
(2) that Gallaudet was subject to a non-transferable duty to inspect its sprinkler systems and that
Gallaudet’s transfer or attempted transfer of this duty caused, in whole or in part, the damages in
this case, and (3) that Guest Services negligently denied Capitol Sprinkler access to the sprinkler
system. Based on Capitol Sprinkler’s Supplemental Brief, it appears that all three negligence
arguments rely on NFPA 25 for the applicable standard of care. See Def.’s Suppl. Br. at 11
(“[b]ecause NFPA 25 carries the force of law in the District of Columbia, and because any
obligations imposed by NFPA 25 on the Gallaudet University . . . are also imposed upon Guest
Services as property manager, the only remaining question before the Court is whether the
requisite standard of care imposed upon Guest Services is clearly defined by the NFPA 25
without the need of [sic] any expert testimony”). Because the Court finds that expert testimony
is necessary to support Capitol Sprinkler’s interpretation of NFPA 25 as asserted in its Motion
for Summary Judgment, Capitol Sprinkler cannot prevail on its negligence defenses to St. Paul’s
claims, and cannot prevail on its negligence claim against Guest Services.
The Court notes that Capitol Sprinkler’s second negligence argument also fails because it
is unsupported by any applicable legal authority. Specifically, Capitol Sprinkler had previously
argued in its summary judgment briefing that Gallaudet (as subrogee for St. Paul) had a non-
transferrable duty to inspect its sprinkler systems based on a distinction found in NFPA 25 that,
according to Capitol Sprinkler, allows a building owner to transfer “authority” to inspect
19
sprinkler systems but prevents the transfer of the “responsibility” to perform such inspections.
See Def.’s Reply to Pl.’s Opp’n at 9-10. Because Capitol Sprinkler did not proffer any expert
testimony supporting this interpretation, the Court requested briefing as to
the basis for Gallaudet’s allegedly non-transferrable duty to inspect its sprinkler
systems (i.e., that NFPA 25 incorporates the distinction between ‘authority’ and
‘responsibility’ that Capitol Sprinkler identifies), and that Gallaudet’s transfer or
attempted transfer of this duty caused, in whole or in part, the damages in this
case.
Order at 2 (Sept. 2, 2008).
Having reviewed the parties’ Supplemental Briefs, it is entirely unclear how Capitol
Sprinkler reaches its conclusion that a building owner cannot delegate its duty to perform
sprinkler inspections. Capitol Sprinkler makes the naked assertion that “Gallaudet University
has a non-delegable statutory duty under D.C. Code § 6-701.01, et seq., to ensure that the
sprinkler system in the Kellogg Conference Center is properly installed and maintained.” Def.’s
Suppl. Br. at 10. If such a non-delegation provision exists in the D.C. Code, the Court is unable
to find it in Section 6-701.01 and its related provisions, which are focused on the duties of
building owners to provide fire escapes and other fire protections but make no mention of
sprinkler systems. Capitol Sprinkler points to no language in this or any related provision even
referencing delegation (or a prohibition on delegation) of an owner’s duties, and as St. Paul
correctly observes, non-delegation arguments have been raised and rejected in numerous other
contexts. See, e.g., Pl.’s Suppl. Br. at 16 (citing Herbert v. District of Columbia, 716 A.2d 196
(D.C. 1998)). Capitol Sprinkler sets forth no reason why application of a non-delegation doctrine
would be appropriate as to the obligations at issue in this case.
In addition to the D.C. Code provision discussed above, Capitol Sprinkler also supports
20
its argument by reference to two provisions in NFPA 25:
Where the property owner is not the occupant, the property owner shall be
permitted to pass on the authority for inspecting, testing, and maintaining the fire
protection systems . . .
Where an occupant, management firm, or managing individual has received the
authority for inspection, testing, and maintenance, the occupant, management
firm, or managing individual shall comply with the requirements identified for the
owner or occupant throughout this standard.
See Def.’s Suppl. Br. at 11 (quoting NFPA 25 §§ 4.1.2.3, 4.1.2.4 (2002)). Capitol Sprinkler
argues that the “plain language” of these provisions means that “the legal duty to ensure that a
sprinkler system is properly inspect [sic] and maintained falls on the owner.” Id. While it may
be true that such a legal duty exists, these provisions do not indicate that such a duty cannot be
delegated to a third-party. Accordingly, if non-delegation can somehow be divined from the
provisions of NFPA 25 or otherwise, Capitol Sprinkler has failed to set forth any evidence in
support of the same.
Finally, all three of Capitol Sprinkler’s negligence arguments fail for the additional
reason that Capitol Sprinkler cannot establish the non-contractual applicability of NFPA 25 in
this case without expert testimony. Whereas a jury may find that the NFPA 25 was incorporated
as a term of the Inspection Agreement (and thereby obligated the parties to comply with its
provisions), the same cannot be said about Capitol Sprinkler’s negligence arguments, which
depend on the applicability of NFPA outside the context of the Inspection Agreement.
In its Supplemental Brief, Capitol Sprinkler argues that NFPA 25 carries the “force of
law” in the District of Columbia because “[t]he D.C. Counsel has adopted a Code of D.C.
Regulations that expressly adopt the ICC International Fire Code as a uniform standard for fire
protection systems” and that, under this code, NFPA 25 is the required standard for inspections.
21
Id. at 10. Capitol Sprinkler urges the Court to accept NFPA 25 as the applicable standard of care.
Id. at 12 (“this Court as well as a jury[] may consider a breach [of NFPA 25] as negligence”).
Capitol Sprinkler’s arguments fundamentally misunderstand what is required before a regulation
such as NFPA 25 may be submitted to the jury as an applicable standard of care.
In the District of Columbia, courts have “required expert testimony to explain the
applicability of statutes where the statute is relied upon as establishing the standard of care.”
McNeil Pharmaceutical v. Hawkins, 686 A.2d 567, 583 (D.C. 1996). For example, in McNeil
Pharmaceutical, the D.C. Court of Appeals examined whether, in the context of a products
liability claim, the trial court properly submitted various statutes and regulations to the jury
where “the only evidence of a standard of care presented to the jury” were the statutes and
regulations. Id. at 579. The court held that “complex or technical statutes . . . may not be used
for negligence per se purposes without expert testimony or guidance from the court to assist the
jury’s understanding.” Id. It was incumbent on the court to determine whether the regulation
“could be reasonably understood by the jury without expert testimony or guidance by the court.”
Id. at 581.
Similarly, in Lowrey v. Glassman, the plaintiff asserted that the reconfiguration of a
hospital’s parking lot violated applicable zoning requirements and caused damage to his
property. 908 A.2d 30 (D.C. 2006). The plaintiff failed to designate a zoning expert, however,
arguing that “expert witnesses were not needed to show the configuration of the parking spaces
or the fact that the spaces violated applicable zoning regulations.” Id. at 36. The D.C. Court of
Appeals summarily rejected that argument because “someone would have to explain to a
factfinder what regulations applied and how they are construed. These are the things with which
22
zoning inspectors – and not lay persons – are familiar.” Id. (internal quotations omitted).
Because “[t]hat information was not available,” the court found that “there was no ‘significant
probative evidence’ in the record tending to support the claim of a zoning violation ‘such that a
reasonable [fact-finder] could return a verdict’ for [the plaintiff].” Id. (quoting Anderson v.
Liberty Lobby, Inc., 477 U.S. 242, 248-49 (1986)). See also Lewis v. Wash. Metro. Area Transit
Auth., 463 A.2d 666, 674 (D.C. 1983) (finding that the trial court erred by admitting into
evidence two provisions of a building code as evidence of negligence because the plaintiff failed
to “proffer any evidence regarding the purpose and scope of the two building code sections or the
meaning of the key terms in them”).
Based on this guidance, the Court finds that Capitol Sprinkler must present expert
testimony concerning both the applicability of NFPA 25 and the meaning of its relevant
provisions.6 This is particularly necessary in the present case because the parties dispute whether
NFPA 25 has, in fact, been adopted as set forth in Capitol Sprinkler’s Supplemental Brief. See
Pl.’s Suppl. Br. at 13 (“[w]hile plaintiff agrees that NFPA 25 is the standard of care which
governs sprinkler system inspections, plaintiff does not agree that NFPA 25, in and of itself,
carries the force of law. Rather it is a national technical standard which is the recognized
standard of care in the sprinkler inspection industry”). In the absence of expert testimony, the
6
The Court notes that there are other issues likely requiring expert testimony. For
example, Capitol Sprinkler would also have to show that the regulation was designed to protect a
class of persons or entities of which Capitol Sprinkler is a member, or that the regulation was
designed to prevent the type of accident that occurred. See McNeil Pharmaceutical, 686 A.2d at
579 (explaining that a statute or regulation may constitute an appropriate standard of care only if
it is “‘enacted to protect persons in the plaintiff’s position or to prevent the type of accident that
occurred’”) (quoting Joy v. Bell Helicopter Textron, Inc., 999 F.2d 549, 557 (1993)). Capitol
Sprinkler has made no effort to set forth credible evidence relating to this issue.
23
Court finds that Capitol Sprinkler’s negligence arguments are non-cognizable. Accordingly, the
Court shall grant Guest Services’s Motion for Summary Judgment as to Capitol Sprinkler’s
negligence claim against Guest Services.7
C. Remaining Issues
Two issues remain. First, Capitol Sprinkler raised a new theory of liability for the first
time in its Supplemental Brief. According to this new theory, St. Paul and Guest Services may
be held liable in this case for violating a common law “innkeeper” standard of care. See Def.’s
Suppl. Br. at 7-9. Capitol Sprinkler argues that, “as the owner of the Kellogg Conference Center,
plaintiff had the same legal duty incumbent upon all inkeepers [sic] by District of Columbia law
i.e., to exercise reasonable care to protect its guests.” Id. at 7. These duties include “tak[ing]
reasonable precautions to protect its guests[] from damages that can be reasonably anticipated.”
Id. at 8. Based on this common law standard, Capitol Sprinkler reaches the following
conclusion:
both plaintiff and Guest Services, by virtue of their contractual relationship, each
had a duty to ensure the safety of the guests of the hotel, which included the duty
to inspect. Therefore, in the absence of any inspection of the drum drip in room
5200 by Capitol Sprinkler, regardless of the reason, the duty to ensure that the
drum drip was in proper working order, so as to protect the guests of the Kellogg
Conference Center, falls to Gallaudet and/or Guest Services.
Id. at 9.
7
In its September 2, 2008 Order and Memorandum Opinion, the Court also held in
abeyance Capitol Sprinkler’s [57] Motion for Summary Judgment against St. Paul to the extent
that it argued that Gallaudet, as the subrogee for St. Paul, was negligent for conduct that was
unrelated to the conduct of Guest Services. Consistent with the analysis set forth above, Capitol
Sprinkler cannot prevail on its negligence-based arguments in the absence of expert testimony
and, accordingly, the Court shall deny the portion of Capitol Sprinkler’s Motion for Summary
Judgment previously held in abeyance in the Order accompanying this Memorandum Opinion.
24
The problems with Capitol Sprinkler’s new theory of liability are easily identifiable.
First, and most obvious, none of the parties in this lawsuit is a former guest of the conference
center suing for damages based on a broken sprinkler system. Whatever duty of care is owed by
Gallaudet to its guests surely is not implicated by the parties and issues in this case. Second, the
undisputed facts in the record demonstrate that Gallaudet (through Guest Services) contractually
delegated its duty to Capitol Sprinkler to inspect the dry sprinkler system. Thus, even if
Gallaudet had a common law obligation based on its status as an innkeeper, Capitol Sprinkler
fails to explain why Gallaudet retained the obligation after Capitol Sprinkler agreed to assume it.
Third, Capitol Sprinkler sets forth no credible evidence that the innkeeper common law standard
of care would include the obligation to drain a drum drip in a dry sprinkler system.
The second and last issue concerns the possible introduction of hearsay statements by the
unidentified escort who accompanied Capitol Sprinkler’s inspectors during its inspection of the
Kellogg Conference Center. The Court’s September 2, 2008 Order required Capitol Sprinkler to
set forth a theory of admissibility concerning the escort’s statements. See Order at 2 (Sept. 2,
2008). Because the Court’s foregoing rulings significantly change the posture of this case, the
Court shall decline to issue any rulings concerning these statements at this time. The Court shall
instead set a schedule for the parties to file pre-trial Motions in Limine, which may include a
motion by St. Paul to exclude the escort’s statements, if deemed appropriate at that time.
IV. CONCLUSION
For the reasons set forth above, the Court shall GRANT St. Paul’s [48] Motion for Partial
Summary Judgment as to liability on its breach of contract claim, and GRANT Guest Services’s
[59] Motion for Summary Judgment, both of which were previously held in abeyance on
25
September 2, 2008. The Court shall dismiss Guest Services from further proceedings in this
case. By separate Order, the Court shall set a Status Hearing to discuss further proceedings for
the two remaining claims in this case – St. Paul’s breach of contract claim (as to which liability
has been established) and St. Paul’s negligence claim (as to which St. Paul did not move for
summary judgment).
Date: June 15, 2009
/s/
COLLEEN KOLLAR-KOTELLY
United States District Judge
26