Affirmed and Substitute Opinion filed July 6, 2023.
In The
Fourteenth Court of Appeals
NO. 14-20-00250-CV
CENTERPOINT ENERGY HOUSTON ELECTRIC, LLC, Appellant
V.
HOWARD E. COLEMAN AND COLEMAN UPHOLSTERY, INC.,
Appellees
On Appeal from the 295th District Court
Harris County, Texas
Trial Court Cause No. 2012-19169
OPINION
We issued our original opinion in this case on March 24, 2022. Both sides
filed motions for rehearing. We overrule the motions for rehearing, withdraw our
previous opinion, and issue this substitute opinion.
In the aftermath of a fire that destroyed buildings, equipment, and vehicles,
Howard E. Coleman and his business Coleman Upholstery, Inc. (collectively,
“Coleman”) sued CenterPoint Energy Houston Electric, LLC, alleging that
CenterPoint’s negligence in relation to maintenance of an electrical transformer on
the property caused the fire. After a jury found CenterPoint’s negligence
proximately caused Coleman’s damages, the trial court remitted a portion of the
damages and entered a final judgment awarding Coleman $5,835,044.49 plus post-
judgment interest. Both sides appealed.
In its first issue, CenterPoint contends that the trial court lacked subject
matter jurisdiction because Coleman failed to exhaust his administrative remedies
with the Public Utility Commission (PUC) before filing this lawsuit. In its second,
third, and fourth issues, CenterPoint challenges the sufficiency of the evidence to
support the jury’s findings that CenterPoint breached the applicable standard of
care and proximately caused Coleman’s damages and the amount of damages
awarded by the trial court. And in its fifth issue, CenterPoint contends the trial
court erred in overruling CenterPoint’s objections to certain evidence relating to
alleged injury to personal and business credit.
In one cross-appeal issue, Coleman asserts that the trial court erred in
remitting a portion of the damages found by the jury. Finding no error in the
judgment, we affirm.
Background
In the early morning of October 15, 2010, a fire started on the premises of
Coleman Upholstery, an automobile upholstery business owned by Howard
Coleman. The fire resulted in significant damage to buildings, equipment, and
vehicles on the Coleman property as well as damage to a neighboring property.
The apparent origin of the fire—near a utility pole at the edge of the Coleman
property—was captured by a security camera on the Coleman premises.
About five weeks before the fire, Coleman experienced a power outage after
2
the transformer on the utility pole was reportedly emitting sparks and later a loud
popping sound. In two visits to the property, CenterPoint technicians performed
repairs and restored power.
At the conclusion of their investigation after the fire, Harris County Fire
Marshal investigators concluded, based on several indicators, that the fire
originated
within the immediate vicinity of the electrical distribution pole located
between the two properties. Video surveillance cameras capture[d] an
initiating event within the area of origin at 2:43:21. The initiating
event captured on video is an intense, brief illumination characteristic
of electrical activity.
Investigators observed that a large copper ground wire (approximately
1/4” to 3/8” in diameter) running from the transformer on the
electrical distribution pole to the ground was unaccounted for. Two
small sections of the ground wire were secured to the pole in line with
the path that would have traveled from ground to the transformer.
Several portions of melted copper were found in the soil at the base of
the pole. The soil at the base of the pole was covered with many
smaller pieces of copper.
Copper typically melts at 1981 degrees Fahrenheit. Outdoor fires
consuming ordinary combustibles such as wood will not typically
reach the temperatures necessary to melt copper. The intensity of
damage to the copper ground wire is indicative of an electrical
anomaly. It is probable that this fire was the result of the ignition of
dry vegetation from a fugitive spark or ember that result[ed] from an
unspecified electrical anomaly from the electrical distribution system.
In 2012, Coleman and the owners of the neighboring property sued
CenterPoint for damages resulting from the fire, alleging that CenterPoint’s
negligence in relation to maintaining the transformer and related equipment caused
the fire. The plaintiffs designated Michael McGraw as their expert regarding the
transformer and the cause of the fire. CenterPoint filed a motion to exclude
3
McGraw’s testimony, asserting that he was not qualified to opine regarding the
cause of the fire, the workings of the transformer, or the standards of care
applicable to a utility. The trial court granted the motion to exclude McGraw’s
testimony and a subsequent no-evidence motion for summary judgment, the
plaintiffs appealed, and we reversed and remanded in a prior opinion, holding
McGraw was qualified to testify. Cura-Cruz v. CenterPoint Energy Houston
Electric, LLC, 522 S.W.3d 565 (Tex. App.—Houston [14th Dist.] 2017, pet.
denied).
On remand, the owners of the neighboring property settled with CenterPoint
and trial proceeded only on Coleman’s claims. The jury heard testimony from
Coleman, his wife, and some of his employees regarding the operation of Coleman
Upholstery and the impact of the fire on the business; the CenterPoint technicians
regarding the work they performed on the transformer; Coleman’s technical expert
McGraw and financial expert James Claywell; and CenterPoint’s technical expert
Jeff Hautanen and financial expert Jeffrey Compton. Other evidence the jury
received included the fire marshal reports, the video showing the start of the fire,
numerous photographs taken of the transformer and the scene of the fire, and
Coleman’s financial statements and tax returns. Because the testimony of each
side’s technical expert is key to multiple issues in this appeal, we will describe it in
some detail here. Other testimony and evidence will be presented as needed in the
analysis section of the opinion.
McGraw, Coleman’s technical expert, began his testimony by detailing his
qualifications and his investigation into the cause of the fire. McGraw has been
involved in circuit design and manufacturing of medium voltage electrical
equipment since 1978, including testing and failure analysis. He concurred with the
fire marshal’s office that the fire was likely caused by an electrical anomaly from
4
the electrical distribution system when a ground fault led to an arc flash or plasma
discharge. McGraw opined that the failure of three safety components contributed
to the cause of the fire: (1) the high-voltage (HV) bushing, an insulated ceramic
device attached at the top of the transformer that functions as the entry point for the
high voltage from the electrical power grid into the transformer and from or near
which the arc flash originated; (2) the external fuse, which should have cleared or
blown, thus stopping the flow of energy, but failed to do so for an extended period
of time; and (3) the copper ground wire that ran from the transformer down the
pole and into the ground and was intended to provide a path for fault current to go
into the ground.
Based on physical evidence he observed at the scene and his interpretation
of the video, McGraw opined that prior to the fire starting, the HV bushing on the
transformer became compromised, permitting an arc flash or uncontained voltage
in or near the HV bushing that first went to the transformer tank and then flashed
over to the equipment ground when the bushing ruptured. When the voltage
proceeded down the ground wire, which McGraw referred to as a “very small
conductor,” the wire was ripped apart, melted, and vaporized. The arc flash then
contacted dry vegetation at the base of the pole, starting the fire. Molten copper
from the ground wire hitting the vegetation may have also contributed to start the
fire. A couple gallons of the insulating mineral oil inside the transformer was
expelled when the HV bushing ruptured and its seal on the transformer broke. The
highly flammable oil likely added fuel to the fire at the base of the utility pole.
During the fire, the external fuse eventually cleared, stopping the voltage and
cutting off power to the security camera. After the fire, the HV bushing was found
to have broken, and the inside of the bushing had black marks that McGraw
identified as carbon from the arc flash. He also observed signs of the arc flash
5
inside the transformer tank, including more black markings and bubbling of the
tank coating.
McGraw opined that the exercise of ordinary and reasonable care
commensurate with the danger involved dictated that each of these three safety
components be installed in a proper and dielectrically consistent manner and
maintained in good working condition to prevent an event like the one in question
from occurring. 1 He explained that it is necessary to regularly inspect, maintain,
and repair or replace these three safety components to keep them in good working
condition and, in reasonable scientific and engineering certainty, if the three safety
components are maintained in good working condition through proper installation,
inspection, maintenance, repair, and replacement, it is more likely than not that
they will not fail and instead will work properly and thereby prevent an event like
the one in question from occurring. And this can be accomplished at a reasonable
cost consistent with good business practices, reliability, safety, and expedition.
McGraw specifically faulted CenterPoint because its technicians, who
responded to the power outage five weeks before the fire, only performed, in the
words of one of the technicians, a “cursory visual inspection” of the transformer
components and did not conduct diagnostic testing to determine the cause of the
earlier problems. He said that the reported overheating of the bus work and
blowing of the fuse would have caused him concern. He specifically suggested
CenterPoint had a responsibility under the circumstances to conduct either a
“Megger test” or a “high potential test” of the transformer and specifically the HV
bushing to make sure there was no leakage current or compromise to ground.
According to McGraw, although a high potential test can be time-consuming
1
“Dielectric” as an adjective means “[h]aving the property of transmitting electric force
without conduction; insulating.” Concise Oxford English Dictionary 399 (12th ed. 2011).
6
because it requires removing the transformer, a Megger test is not time-consuming
and neither test is expensive to conduct. He further asserted that many of his client
utilities keep handheld Megger devices on their trucks but CenterPoint does not
routinely provide them to their technicians. A Megger device is used to inject
voltage into the equipment being tested and then measure to make sure that no
partial discharges or leakage currents are occurring. He explained that with an oil-
filled transformer, such as the one at issue here, a cursory visual inspection will not
reveal the conditions inside the tank and “the only way you can determine if
something is wrong is to test.”
Referring to recurring issues with the same transformer, McGraw said that
if you get that many service calls on one piece of equipment in a very
short period of time, months, it’s a pretty good indication that that’s a
trouble area and you need to investigate and test more to find out why
you keep having to go back. [I]f it had been my transformer and I kept
having problems with the same transformer and the same service drop
over and over again, I’d be all over it, trying to figure out what it is
that’s really causing all these issues, because ultimately at 19
[kilovolts], if you have a whoops, it’s catastrophic.
McGraw concluded that CenterPoint failed to exercise reasonable judgment
under the circumstances and breached the standard of care. He said that when put
on notice that the transformer had experienced a ground fault, CenterPoint had a
duty to determine the cause rather than just replacing a few components and
putting the transformer back into service.
Regarding the failure of the ground system to contain the voltage, McGraw
indicated the system was too small and too weak for the voltage involved. He
explained that the ground wire came down the utility pole from the transformer,
into the ground, and then went underneath the pole. He said that it needed to be
designed and engineered properly in the beginning, which requires installation in a
7
dielectrically consistent manner for the applied voltages. He suggested had the
ground grid been “stronger, larger,” the wire would likely not have melted.
McGraw did not offer specific criticisms regarding the external fuse other than the
fact that it failed to clear in response to the arc flash and had recently been replaced
by CenterPoint.
On cross-examination, McGraw acknowledged that he could not state the
exact reason why the security camera continued to operate after the fire began. He
further agreed that he had no specific criticism of the work that the technicians
actually performed under the circumstances and could not say that anything they
did caused the fire or was negligent. He admitted he did not know of any specific
utility that had a transformer maintenance program that required high potential or
Megger testing on a regular basis.
CenterPoint’s technical expert, Jeffrey Hautanen, also began his testimony
by describing his qualifications and investigation. Hautanen admitted he did not
know what caused the fire but insisted it was not ignited by an electrical anomaly
from the power system, as determined by McGraw and the fire marshal
investigators. Hautanen noted the presence of metal barrels on the property with
indications that something had been burned inside of them prior to the fire. He also
noted that at least one of the power cords that stretched across the property
exhibited signs of having experienced “arcing effects.” And he noted a battery on
the property that could have been an ignition source and suggested an employee
could have been smoking in the area.
Hautanen went through the video of the fire for the jury and concluded that
the fire did not start at the base of the utility pole but some distance away from the
pole. He also explained that if there had been an electrical system anomaly, one
would expect to see “flutters, fluctuations” on the video and a camera connected to
8
the system would typically “drop out.” He opined instead that the video recording
finally shut off when the fire got into the trees and thereby impacted the main
electricity transmission line.
Hautanen further questioned several of McGraw’s conclusions. He disagreed
with McGraw’s hypothesis that the copper ground wire was ripped apart, melted,
and vaporized by electrical arcing and instead asserted the fire, infused by wind,
had gotten hot enough to melt the copper. Hautanen also rejected the idea that a
flashover had occurred within the transformer tank, stating that there would have
been a loss of metal from the tank itself if that had occurred. He maintained that
the fracturing of the HV bushing and loss of oil from the transformer tank were the
result of high temperatures from the fire and were not related to the cause of the
fire. Hautanen asserted that he tested the transformer after the fire and does not
believe that it failed. He concluded that nothing about the condition of the
transformer components indicated a corona or flashover had developed. He said
that he has never seen fuses on a transformer fail to clear timely; he acknowledged
that there are conditions under which a fuse disconnect can “hang” after a fuse
element blows but asserted that did not occur in this instance.
Hautanen further discounted the fire marshal investigators’ conclusions by
explaining that they look for signs of arson and are not looking to assign cause or
fault for private sector purposes. Accordingly, he said, their investigation is often
preliminary and lacks follow-through testing and analysis. He particularly thought
that their decision to eliminate the power cords on the property as an ignition
source, because none of the breakers to which they were assigned had tripped, was
a poor decision.
On cross-examination, Hautanen stated that he has spent his career as a
forensic engineer, spending 80-90 percent of his time on claims and lawsuits. As of
9
the date of this trial, he had testified in depositions or trials 87 or more times and
had worked in this capacity on behalf of CenterPoint for approximately twenty
years. Hautanen explained that he did not make a determination on the cause of the
fire because some evidence had not been retained, but he acknowledged he was
given unfettered access to the site after the fire. He said that he has never seen a
transformer maintenance program in the United States; instead, utilities rely on
outages and smart meters to know when to service transformers.
The jury charge was comprised of only two questions. Question 1 asked,
“Did the negligence, if any, of CenterPoint . . . proximately cause the occurrence in
question?” Negligence was defined in the charge as the “failure to use ordinary
care, that is, failing to do that which a public utility of ordinary prudence would
have done under the same or similar circumstances or doing that which a public
utility of ordinary prudence would not have done under the same or similar
circumstances.” Question 2 was contingent on Question 1 and asked the jury what
sum would compensate Coleman for certain types of possible damages. The jury
answered “yes” to Question 1 and found damages in response to Question 2 in the
amounts of $3,633,917 for past lost profits, $803,957 for past property damage,
$450,000 for past damage to personal and business credit, and $50,000 for future
damage to personal and business credit.
Among other post-judgment filings, CenterPoint moved for a remittitur of
lost profits damages. The trial court then suggested a remittitur, which Coleman
accepted while preserving the right to appeal. The remittitur reduced the amount of
lost profits damages awarded from $3,633,917 to $2,763,435. In an amended final
judgment, the trial court awarded Coleman a total of $5,835,044.49 in damages
and prejudgment interest plus post-judgment interest. Both sides appealed.
I. CenterPoint’s Appeal
10
As stated above, CenterPoint challenges the trial court’s jurisdiction as well
as the sufficiency of the evidence to support liability and damages and the trial
court’s overruling of certain evidentiary objections. We begin our discussion with
the jurisdictional challenge.
A. Jurisdiction
In its first issue, CenterPoint contends that the trial court lacked subject
matter jurisdiction over this dispute because the PUC has exclusive original
jurisdiction over issues underlying Coleman’s claims and Coleman failed to
exhaust administrative remedies with the PUC before filing the lawsuit. Subject-
matter jurisdiction is essential to a court’s power to decide a case and can be raised
at any time. See City of Houston v. Rhule, 417 S.W.3d 440, 442 (Tex. 2013);
Alfonso v. Skadden, 251 S.W.3d 52, 55 (Tex. 2008). 2 Whether a trial court has
subject matter jurisdiction is a question of law, to which we apply a de novo
standard of review. Minton v. Gunn, 355 S.W.3d 634, 639 (Tex. 2011).
1. Governing Law
A line of recent Texas Supreme Court opinions has explored the question of
when common law claims such as torts or breaches of contract fall within the
scope of the PUC’s exclusive original jurisdiction. See In re Oncor Elec. Delivery
Co., 630 S.W.3d 40 (Tex. 2021) (holding personal injury action against utility
alleging negligence and consumer-protection violations stemming from customer’s
sustaining electric shock injuries while trimming tree limbs near a power line did
2
Coleman argues that CenterPoint’s jurisdictional argument is barred by the doctrine of
estoppel by laches. Subject matter jurisdiction, i.e., a court’s power to hear a case, cannot be
created by estoppel. See, e.g., Wilmer-Hutchins I.S.D. v. Sullivan, 51 S.W.3d 293, 294 (Tex.
2001) (per curiam); San Jacinto River Auth. v. Paxton, No. 03-18-00547-CV, 2019 WL
3952829, at *4 (Tex. App.—Austin Aug. 22, 2019, no pet.) (mem. op.). And, as indicated above,
a question regarding a court’s jurisdiction can be raised at any time. See Alfonso, 251 S.W.3d at
55. Coleman does not cite any authority carving out an exception for estoppel by laches.
11
not have to begin in the PUC); In re CenterPoint Energy Houston Electric, LLC,
629 S.W.3d 149 (Tex. 2021) (plurality op.) (holding wrongful-death action against
utility stemming from contact with downed power line and alleging negligence in
the selection of fuse size for the line did not have to begin in the PUC) 3; In re Tex.-
N.M. Power Co., 625 S.W.3d 42 (Tex. 2021) (holding property damage claims
resulting from wooden utility construction mats carried by floodwaters did not
have to begin in PUC); Oncor Elec. Delivery Co. LLC v. Chaparral Energy, LLC,
546 S.W.3d 133 (Tex. 2018) (holding breach of contract action had to begin in the
PUC when plaintiff complained of a failure to timely provide electrical service and
resolution of claims required interpretation of utility’s PUC-approved tariff).
Within these opinions, the court has grappled with the contrasting purposes
of the State’s regulation of public utilities, which “acts as a counterweight to public
utility monopolies, ensuring that they charge fair rates and adequately provide vital
services,” and the tort system, the “fundamental purposes” of which “are to deter
wrongful conduct, shift losses to responsible parties, and fairly compensate
deserving victims.” In re Oncor, 630 S.W.3d at 43 (respectively citing Tex. Util
Code § 31.001 and quoting Roberts v. Williamson, 111 S.W.3d 113, 118 (Tex.
2003)). “Regulation,” the court has further explained, “is the government’s
prospective ordering of marketplace conduct,” while “tort lawsuits are retroactive
case-by-case correctives.” Id. There are, however, circumstances under which tort
and other common law actions must begin in the PUC.
3
In In re CenterPoint, the plurality opinion was joined by four justices. 629 S.W.3d at
152. A concurring justice agreed that under established precedent, the disposition was correct
(“the plaintiffs here are not the ‘kind of “affected person” who may bring a claim to the
Commission’ and have not brought ‘the kind of claim that the Commission can adjudicate’”) but
declined to join the plurality opinion. Id. at 166 (Boyd, J., concurring). Two justices dissented,
and one justice did not participate in the decision. Plurality opinions of the Texas Supreme Court
do not constitute binding precedent but may be cited as persuasive authority. See Cincinnati Life
Ins. Co. v. Cates, 927 S.W.2d 623, 626 (Tex. 1996); D.M. Diamond Corp. v. Dunbar Armored,
Inc., 124 S.W.3d 655, 659 n.6 (Tex. App.—Houston [14th Dist.] 2003, no pet.).
12
As instructed by the supreme court, our analysis of this issue begins with the
presumption that district courts are constitutionally empowered to resolve legal
disputes. See Chaparral Energy, 546 S.W.3d at 138; see generally Tex. Const. art.
V, § 8. To overcome that presumption, the constitution or a statute must grant
exclusive jurisdiction to another court or an administrative agency. See Chaparral
Energy, 546 S.W.3d at 138. Administrative agencies do not enjoy the jurisdictional
presumption of district courts but are legislative creations with only such powers as
are expressly conferred and necessary to accomplish their duties. See id. A state
agency has exclusive original jurisdiction when the legislature has granted the
agency sole authority to make an initial determination in a dispute. Id. When an
agency has exclusive jurisdiction, courts lack jurisdiction until the party has
exhausted all available administrative remedies before the agency. Id. Whether an
agency has exclusive jurisdiction is a question of statutory interpretation that we
review de novo. Id. It is the burden of the party resisting the district court’s
jurisdiction to demonstrate that an agency has exclusive original jurisdiction. In re
Oncor, 630 S.W.3d at 44–45; In re CenterPoint, 629 S.W.3d at 156.
The legislature may grant an agency exclusive original jurisdiction via either
of two methods. A statute expressly grants an agency exclusive jurisdiction when
its language clearly expresses an intent for the agency to have exclusive
jurisdiction over matters governed by the statute. Chaparral Energy, 546 S.W.3d at
138. In the absence of an explicit grant, an agency may still have exclusive
jurisdiction when a “pervasive regulatory scheme” indicates the legislature
intended for the regulatory process to be the exclusive means of remedying the
problem to which the regulation is addressed. Id.
CenterPoint is a public electric utility regulated by the PUC. 4 The Texas
4
The PUC’s authority is to some degree limited based on geographical location. It is
13
Public Utility Regulatory Act (PURA) grants the PUC broad powers to “regulate
and supervise the business of each public utility within its jurisdiction and to do
anything specifically designated or implied by [PURA] that is necessary and
convenient to the exercise of that power and jurisdiction.” Tex. Util. Code §
14.001. In regard to electric utilities, the purpose of PURA “is to establish a
comprehensive and adequate regulatory system . . . to assure rates, operations, and
services that are just and reasonable to the consumers and to the electric utilities.”
Id. at 31.001(a). The PUC’s jurisdiction is limited in part by the legislature’s stated
objective in enacting PURA, that it was “for the purpose of regulating rates and
services so that such rates may be fair, just, and reasonable, and the services
adequate and efficient.” In re Oncor, 630 S.W.3d at 46 (quoting Public Utility
Regulatory Act, 64th Leg., R.S., ch. 721, sec. 17(a), 1975 Tex. Gen. Laws 2327,
2334–35 (codified at Tex. Rev. Civ. Stat. art. 1446c, § 17)). That the PUC was
created as a regulatory body also provides a limitation on its authority to adjudicate
disputes; essentially, it cannot adjudicate what it does not regulate. See id. at 46-47.
Within that limitation, PURA grants the PUC exclusive original jurisdiction both
expressly and by the creation of a “pervasive regulatory scheme.” See In re
CenterPoint, 629 S.W.3d at 156; Chaparral Energy, 546 S.W.3d at 139. The
question then is whether Coleman’s claims fall within the scope of the exclusive
original jurisdiction provided in PURA such that they must start their path toward
resolution at the PUC. 5 CenterPoint argues that the PUC has exclusive original
jurisdiction in this case both because Coleman is an “affected person” expressly
undisputed in this case that the property in question was within the PUC’s area of primary
authority. See generally Tex. Util. Code §§ 32.001, 33.001(a).
5
When issues underlying a claim fall within the PUC’s jurisdictional scope but the
complaining party seeks a remedy that the PUC cannot provide, such as damages, resolution may
require a two-step process, where the PUC first resolves questions within its purview and then a
court determines the remaining issues necessary for resolution of the claim. See Chaparral
Energy, 546 S.W.3d at 141-42.
14
eligible to file a complaint under PURA and because Coleman’s claims involve
underlying issues that fall within PURA’s pervasive regulatory scheme. We will
address each assertion in turn.
2. “Affected Person”
Pursuant to Utilities Code section 15.051, “[a]n affected person may
complain to the regulatory authority in writing setting forth an act or omission by a
public utility in violation or claimed violation of a law that the regulatory authority
has jurisdiction to administer or of an order, ordinance, or rule of the regulatory
authority.” Tex. Util. Code § 15.051. As relevant here, the Code defines “affected
persons” as persons “whose utility service or rates are affected by a proceeding
before a regulatory authority.” Id. § 11.003(1)(B).
CenterPoint first emphasizes that Coleman was a CenterPoint customer at
the time of the fire and Coleman’s claims allege negligence in regard to equipment
that provided electrical services to Coleman’s property. CenterPoint insists that
Coleman was an “affected person” under PURA because he was a customer
“whose utility service [would be] affected” by a proceeding before the PUC. Id.
CenterPoint further asserts that any determination regarding whether it was
negligent in its maintenance of the transformer and other equipment “would
directly impact the manner in which CenterPoint provides electrical service to
Appellees and its other customers.”
Although Coleman was undoubtedly a customer at the time of the fire, his
claims do not complain about his rates or his service. As described in detail above,
Coleman alleges that CenterPoint’s negligence in regard to the transformer and
related equipment caused a fire on his property. Coleman does not complain about
rates charged, a failure to provide timely service, the adequacy of his service, or an
interruption to his service. In In re Oncor, the supreme court concluded that an
15
electric utility may not compel a plaintiff who alleges a common law personal
injury claim to initiate the claim in the PUC unless the claim complained about
rates or the provision of electrical service (i.e., “lights on or off” as the supreme
court phrased it). 630 S.W.3d at 43; see also In re CenterPoint, 629 S.W.3d at 157
(explaining that plaintiffs in that case were not “affected persons” under PURA
because “none of the issues underlying their claims complain of a statutory or
regulatory violation affecting their utility service or rates.”). The same reasoning
can be applied in this case where Coleman does not complain about rates or
services. CenterPoint’s argument that Coleman was an affected person because the
manner in which it provides services to all of its customers could be impacted by a
determination in this case shoots too broadly. If that were the standard, it is
difficult to imagine a lawsuit in which a utility could not claim that a determination
in the case would impact how it operated in the future. That is not the standard.
The court in In re Oncor further noted that the personal injury claim in that
case could just as easily have been brought by a noncustomer and arose in part
from Oncor’s duty to maintain premises that it occupied, i.e., its utility easement
across the plaintiff’s property. 630 S.W.3d at 49 (“While the provision of
electricity service (and its timeliness) falls squarely in the regulatory sphere, a duty
alleged against an occupier of the premises does not.”). Here, Coleman essentially
alleged his damages resulted from CenterPoint’s failure to properly maintain its
equipment, which was on a utility easement on Coleman’s property. Although
Coleman received services from CenterPoint, his complaint is not about the
services but about CenterPoint’s alleged failure to properly install, inspect,
maintain, repair, and replace its equipment to avoid starting a fire. More
specifically, Coleman alleged CenterPoint’s negligence resulted in the equipment
failing to contain the voltage coming into the transformer, which resulted in the
16
ignition of dry vegetation at the base of the utility pole on Coleman’s property.
CenterPoint offers no argument as to why Coleman could not have made the same
claim had he not been a CenterPoint customer, for example, if his property had
been undeveloped and not receiving electrical services or, as occurred for the other
original plaintiffs in this very lawsuit, he had owned a neighboring property to the
one with the utility pole and easement. The mere fact that Coleman’s claims may
be tangentially related to the fact that he was receiving electrical services from
CenterPoint does not render him an affected person under PURA. See id. at 43.
3. Pervasive Regulatory Scheme
Additionally, the PUC does not possess exclusive original jurisdiction over
Coleman’s claims under PURA’s pervasive regulatory scheme because Coleman’s
allegations do not concern issues that the PUC actually regulates. See id. at 47
(explaining that PUC adjudicatory jurisdiction is limited to issues that implicate
regulatory matters), 51 (explaining that the legislature has not commanded that
agency jurisdiction turns solely on whether the injured party “happens to be a
utility customer or other ‘affected person’”); In re CenterPoint, 629 S.W.3d at 161-
64 (holding that although PUC had exclusive jurisdiction to regulate issues
underlying plaintiff’s claims, because it had not done so and no other law that it
was empowered to adjudicate did so, it did not have jurisdiction to adjudicate
those issues).
At the outset, we note that CenterPoint has misconstrued Coleman’s
allegations. CenterPoint describes Coleman’s allegations as asserting CenterPoint
negligently failed to (1) adopt a formal, proactive maintenance program for its
transformers and (2) provide all of its service technicians with Megger devices and
mandate the regular use of such devices in maintaining its transformers.
CenterPoint, however, does not cite to where Coleman alleged either of these
17
things, much less limited himself to these theories.
As set forth in detail above, McGraw, Coleman’s technical expert, generally
asserted that CenterPoint’s failure to properly install, inspect, maintain, repair, and
replace its equipment proximately caused the fire. More specifically, he faulted
CenterPoint for only visually inspecting the transformer and related equipment
after having repeated problems and not conducting diagnostic testing. He opined
that given the history of problems, CenterPoint had a responsibility to conduct
either a “Megger test” or a “high potential test” of the transformer and HV bushing
to make sure there was no leakage current or compromise to ground rather than
just replacing a few components and putting the transformer back into service.
According to McGraw, “if you get that many service calls on one piece of
equipment in a very short period of time, months, it’s a pretty good indication that
that’s a trouble area and you need to investigate and test more to find out why you
keep having to go back.” McGraw additionally criticized the size and strength of
the ground grid attached to the transformer, explaining that it required installation
in a dielectrically consistent manner for the applied voltages.
Although McGraw mentioned that many of his client utilities keep handheld
Megger devices on their trucks, he did not specifically fault CenterPoint for failing
to provide all of its technicians with Megger devices and mandate the regular use
of such devices in maintaining its transformers, as CenterPoint suggests. Instead,
McGraw merely said that they should have performed diagnostic testing under the
circumstances presented in this case. Likewise, while McGraw suggested that a
formal service program for transformers would be “valuable to their system,” he
did not testify that CenterPoint breached the standard of care in this case by failing
to have a formal, proactive maintenance program for all of it transformers. Again,
instead, he faulted CenterPoint for not performing diagnostic testing on this one
18
transformer and related equipment under the circumstances presented and for not
properly installing, inspecting, maintaining, repairing, and replacing its equipment.
That said, we turn to the question of whether the issues underlying these
claims fall within the scope of the PUC’s adjudicatory jurisdiction. As discussed,
at the heart of the allegations is whether CenterPoint properly installed, inspected,
maintained, repaired, and replaced its equipment and whether it had a duty to
perform diagnostic testing on the transformer and related equipment given its
alleged recent history of problems or whether simply replacing some components
and placing the transformer back in service met the applicable standard of care. As
described below, we conclude that none of the PUC regulations cited by
CenterPoint displace the common-law standard of care with respect to these issues
and whether that standard has been met in individual cases is not a question of
rules or regulations within the PUC’s purview. See In re CenterPoint, 629 S.W.3d
at 162. Accordingly, PURA’s pervasive regulatory scheme does not give the PUC
exclusive original jurisdiction because the parties’ dispute does not involve PUC
regulatory action. See id. at 163.
CenterPoint cites three provisions of the Texas Administrative Code, Title
16, in support of its position that the PUC regulates these issues. 16 Tex. Admin.
Code §§ 25.52(b)(1), (4), 25.101(d). The portions of these provisions on which
CenterPoint relies read as follows:
• Section 25.52(b)(1): “Every utility shall make all reasonable efforts to
prevent interruptions of service.”
• Section 25.52(b)(4): “Each utility must maintain adequately trained
and experienced personnel throughout its service area so that the
utility is able to fully and adequately comply with the service quality
and reliability standards.”
19
• Section 25.101(d): “Each electric utility shall construct, install,
operate and maintain its plant, structures, equipment, and lines in
accordance with [provisions of the American National Standards
Institute, Inc., the National Electrical Safety Code, and such other
codes and standards that are generally accepted by the industry].”
CenterPoint contends that these provisions sufficiently regulate the
maintenance of electrical equipment by a utility such that the PUC has exclusive
jurisdiction to determine whether it met the applicable standards. CenterPoint made
a similar argument in In re CenterPoint, which involved a question of whether
CenterPoint had employed a properly-sized fuse on electrical lines. 629 S.W.3d at
162. Indeed, in that case, CenterPoint cited both sections 25.52(b)(1) and
25.101(d). A plurality of the supreme court, however, expressly rejected these
provisions as being too general to supply a standard of care in a negligence case,
stating “regulations generally requiring a party to act safely or reasonably do not
substitute a legislatively imposed standard of conduct for the reasonable person
standard of common-law negligence.” Id. at 163 (citing, e.g., Entex, a Div. of
Noram Energy Corp. v. Gonzalez, 94 S.W.3d 1, 8–9 (Tex. App.—Houston [14th
Dist.] 2002, pet. denied)).6 Although the In re CenterPoint court did not address
section 25.52(b)(4), regarding maintaining a trained and experienced staff, that
provision likewise appears too general to provide a standard. CenterPoint does not
cite any other law or regulations as proof that the PUC specifically regulates the
installation, inspection, maintenance, repair, or replacement of transformers and
associated equipment. If the PUC does not regulate the issues underlying
Coleman’s claims pursuant to PURA’s pervasive regulatory scheme, it does not
6
A fifth justice, concurring in the disposition, also agreed that the plaintiff in In re
CenterPoint had not brought “the kind of claim that the Commission can adjudicate.” 629
S.W.3d at 166 (Boyd, J., concurring); see also supra n.4.
20
have exclusive original jurisdiction to adjudicate Coleman’s claims. See id. at 161-
64. 7
4. Conclusion
The PUC does not have exclusive original jurisdiction over the underlying
issues in this case by express grant or under PURA’s pervasive regulatory system.
Accordingly, Coleman was not required to exhaust any administrative remedies
and the trial court possessed subject matter jurisdiction over Coleman’s claims. We
overrule CenterPoint’s first issue.
B. Sufficiency of the Evidence
A negligence claim requires proof of circumstances giving rise to a legal
duty owed by the defendant to the plaintiff, a breach of that duty, and damages
proximately caused by that breach. Lee Lewis Constr., Inc. v. Harrison, 70 S.W.3d
778, 782 (Tex. 2001); Davis-Lynch, Inc. v. Asgard Techs., LLC, 472 S.W.3d 50, 63
(Tex. App.—Houston [14th Dist.] 2015, no pet.). In its second, third, and fourth
issues, CenterPoint challenges the sufficiency of the evidence to support the jury’s
findings that CenterPoint breached the applicable standard of care and proximately
caused Coleman’s damages and the amount of damages awarded by the trial court.
When examining a legal-sufficiency challenge, we review the evidence in
the light most favorable to the challenged finding and indulge every reasonable
inference that would support it. City of Keller v. Wilson, 168 S.W.3d 802, 822
7
It is not entirely clear whether CenterPoint intended to argue that the PUC has exclusive
original jurisdiction because resolution of the underlying issues allegedly require interpretation
of CenterPoint’s PUC-approved tariff. To the extent that CenterPoint intended to do so, we note
that in the prior appeal, we held that the “Good Utilities Practice” required in the tariff did not
impose a new or additional standard that was different than the common law duty of care. See
Cura-Cruz, 522 S.W.3d at 571-72; see also In re CenterPoint, 629 S.W.3d at 165 (“We see no
indication that the Legislature intended the PUC to resolve issues based on a tariff where no
tariff provisions alter the applicable legal standards.”).
21
(Tex. 2005). We credit favorable evidence if a reasonable factfinder could and
disregard contrary evidence unless a reasonable factfinder could not. Id. at 827.
When a party attacks the legal sufficiency of an adverse finding on which it did not
have the burden of proof, the party must demonstrate on appeal that no evidence
supports the finding. Graham Cent. Station, Inc. v. Pena, 442 S.W.3d 261, 263
(Tex. 2014) (per curiam).
In a factual-sufficiency challenge, we consider and weigh all the evidence,
both supporting and contradicting the finding. Mar. Overseas Corp. v. Ellis, 971
S.W.2d 402, 406–07 (Tex. 1998). We will set aside a finding for factual
insufficiency only if it is so contrary to the overwhelming weight of the evidence
as to be clearly wrong and unjust. Id. at 407. The amount of evidence required to
affirm is far less than the amount necessary to reverse a judgment. Harris Cty. v.
Coats, 607 S.W.3d 359, 381 (Tex. App.—Houston [14th Dist.] 2020, no pet.).
As trier of fact, the jury is the sole judge of witness credibility and may
accept or reject all or part of the testimony provided by any witness. See, e.g.,
Golden Eagle Archery, Inc. v. Jackson, 116 S.W.3d 757, 761 (Tex. 2003). This
generally includes testimony provided by experts. See Gator Gone Safety Pilots v.
Holt, 622 S.W.3d 524, 537 (Tex. App.—Houston [14th Dist.] 2021, no pet.).
1. Breach of Duty
CenterPoint first challenges the legal and factual sufficiency of the evidence
to support the jury’s finding that CenterPoint breached a duty of care owed to
Coleman. CenterPoint generally does not differentiate between its legal and factual
sufficiency arguments. We will begin our analysis by offering a synopsis of
Coleman’s theory of breach, based primarily on expert McGraw’s testimony. We
will then address each of CenterPoint’s specific critiques.
22
As discussed in detail above, McGraw testified that the fire was most likely
caused when an arc flash that originated in or near a compromised HV bushing
destroyed the copper ground wire and then ignited dry vegetation near the base of
the utility pole. Molten copper from the wire and oil expelled from the transformer
through the broken seal of the bushing also likely contributed to the fire. McGraw
opined that three safety components failed, causing or contributing to the cause of
the fire: the HV bushing, an external fuse, and the ground wire. According to
McGraw, had there not been a dielectric and insulation breakdown of the HV
bushing, had the external fuse not failed to clear, or had the ground system been
adequate, the fire never would have started. Moreover, he said that had the
components been properly installed, inspected, maintained, repaired, and replaced,
they would not have failed and, given the level of danger involved, CenterPoint
had a duty of care to properly install, inspect, maintain, repair, and replace those
safety components. McGraw further asserted that CenterPoint had ample warning
of a problem and opportunity to fix any issues but failed to do so, thus breaching
the duty of care.
In support of his conclusions, McGraw cited CenterPoint records and the
deposition testimony of CenterPoint’s technicians. He also cited the video, which
recorded the start of the fire, photographs of the equipment and the burn patterns
on the property taken after the fire, and certain physical evidence including the
appearance of the HV bushing, copper wire, and transformer tank after the event.
The HV bushing was broken and had black marks on it from carbon as a result of
an arc flash. The copper wire was ripped-apart, melted, and vaporized. The
transformer tank had burn marks and a bubbling pattern on the inside, indicating an
arc flash had occurred.
McGraw opined that in reasonable scientific and engineering certainty, if the
23
three safety components are maintained in good working condition through proper
installation, inspection, maintenance, repair, and replacement, it is more likely than
not that they will not fail, and instead will work properly and prevent an event like
the one in question from occurring. He specifically faulted CenterPoint because its
technicians only visually inspected the transformer, HV bushing, and related
equipment and did not conduct a Megger test or other diagnostic test to determine
the cause of earlier equipment troubles. He indicated CenterPoint had a
responsibility under the circumstances to conduct such testing to make sure there
was no leakage current or compromise to ground and not simply replace a couple
of components and restore power. He said that
if you get that many service calls on one piece of equipment in a very
short period of time . . . it’s a pretty good indication that that’s a
trouble area and you need to investigate and test more to find out why
you keep having to go back . . . because ultimately at 19 [kilovolts], if
you have a whoops, it’s catastrophic.
McGraw also questioned the adequacy of the ground system, the failure of
which he said likely caused or contributed to causing the fire. He insisted the
system should have been installed in a dielectrically consistent manner for the
applied voltages and had it been “stronger, larger,” it likely would not have failed
to contain the voltage in this case. McGraw concluded that CenterPoint’s failure to
maintain its equipment in good working condition through proper installation,
inspection, maintenance, repair, and replacement was a proximate cause of the fire.
The fire marshal investigators concurred that the fire probably started when
an unspecified electrical anomaly from the electrical distribution system ignited
dry vegetation at the base of the utility pole. Although CenterPoint’s expert,
Hautanen, criticized both McGraw and the fire marshal’s conclusions, he did not
offer a strong alternative hypothesis for how the fire started, suggesting
24
possibilities like burn barrels and extension cords that were rejected by McGraw
and the investigators. Hautanen also disagreed with McGraw and the investigators’
interpretation of the video of the fire.
CenterPoint begins its challenge to the evidence of breach by asserting that
Coleman was required and failed to present evidence of three predicates: “(1) the
transformer caused the fire, (2) the transformer’s components were defective, and
(3) CenterPoint negligently maintained the transformer.” We will interpret
CenterPoint’s argument as including equipment related to the transformer as
discussed by McGraw in his testimony.
Did the transformer cause the fire? Regarding the first alleged predicate,
that the transformer or related equipment caused the fire, McGraw cited significant
evidence indicating an arc flash that originated in or near the HV bushing—and
then escaped the transformer through the ruptured bushing and destroyed the
copper ground wire—produced sparks that ignited dry vegetation at the base of the
utility pole. According to McGraw, molten copper from the wire and oil expelled
from the transformer also contributed to the fire. The cited evidence included video
and photographic evidence as well as the physical evidence discussed above,
including the broken HV bushing, the ripped-apart, melted, and vaporized copper
ground wire, and the burn marks and bubbling pattern inside the transformer tank.
The fire marshal investigators generally concurred that the fire started as the result
of “an unspecified electrical anomaly from the electrical distribution system,” and
they specifically noted the destroyed copper wire.
CenterPoint, however, argues that there was conclusive evidence that a
ground fault from in or near the transformer could not have started the fire because
the security camera continued to operate for 30 minutes after the fire began.
CenterPoint insists that a fault powerful enough to cause the HV bushing to rupture
25
would have immediately cut off power to the camera. In support, CenterPoint cites
the deposition testimony of William Rhodes, who was initially hired by Coleman
as an expert in the case. Rhodes noted that the transformer could not have suffered
a “catastrophic failure” because the camera kept working. In the excerpt provided,
however, Rhodes did not say that an electrical fault did not occur, just that it was
not “catastrophic.” He did not define what he meant by “catastrophic” in this
context. CenterPoint additionally notes that its own expert, Hautanen, disagreed
with McGraw that the condition of the transformer after the fire indicated an
electrical fault or arc flash had occurred within it, but of course, the jury was free
to accept McGraw’s conclusion over that of Hautanen. See Golden Eagle Archery,
116 S.W.3d at 761; Gator Gone Safety Pilots, 622 S.W.3d at 537. The jury was
also able to see for themselves the photographs of the transformer as an aid for
determining which expert was more credible.
CenterPoint next points out that Hautanen and its technicians testified that
fuses clear almost instantaneously in response to faults and they had never heard of
a fuse taking so long to clear. These witnesses did not testify, however, that it was
impossible for a fuse to fail to clear in response to a ground fault. McGraw
explained that the fuses could have simply delayed in clearing due to the amount of
current involved, saying “in the case of a high resistance ground/flashover, it
would have taken a little bit of time for that fuse to actually clear.” CenterPoint
criticizes McGraw for not offering “detailed support” for this observation and for
not explaining how the fault could have been powerful enough to rupture the HV
bushing and expel oil from the transformer but not clear the fuse. CenterPoint also
asserts, without citing any evidence, that the fault’s impact should have diminished
over time and not increased after 30 minutes to clear the fuse. McGraw indeed
acknowledged that he could not “definitively state . . . the exact reason” why the
26
camera continued to receive power, but such admission is not fatal to his
testimony. It seems apparent that McGraw concluded that there was not enough
information to know exactly why the fuse did not clear for 30 minutes and yet
there was enough information, as he described in detail, to conclude that an arc
flash originating in or near the HV bushing caused the fire. The fire marshal
investigators generally concurred. The jury was free to accept McGraw’s testimony
and the investigators’ conclusions over that of the CenterPoint witnesses, and we
presume that they did so. See Golden Eagle Archery, 116 S.W.3d at 761; Gator
Gone Safety Pilots, 622 S.W.3d at 537.
CenterPoint additionally notes that Hautanen testified the oil in the
transformer would have burned off if there had been a fault, but again, the jury was
free to discount his testimony and accept McGraw’s that the physical evidence
supported the conclusion that a fault had occurred in the transformer. Also, again,
the jury was able to view the photographs of the equipment for themselves as an
aid for assessing credibility. The evidence was legally and factually sufficient to
establish that CenterPoint’s equipment caused the fire on Coleman’s property.
Was there a defect in the transformer’s components? CenterPoint next
argues that even if evidence supported the conclusion that a fault occurred, there
was no evidence or insufficient evidence that the transformer or related equipment
was defective. CenterPoint insists that Coleman needed and failed to detail exactly
how the components were physically or mechanically defective or inadequate and
whether each such defect or inadequacy existed at a point when CenterPoint could
and should have discovered it.
As described by McGraw and others at trial, a key function of the electrical
system and the equipment at issue in this case is the containment of electric current
from the utility grid. The significant evidence that an arc flash occurred in or near
27
the HV bushing, the transformer and the ground system failed to contain the
ground fault, and the fuse failed to clear is evidence that the equipment did not
perform its intended function. McGraw explained that if such equipment is
properly installed, inspected, maintained, repaired, and replaced, it would not have
failed, the current would have been contained, and the fire would not have started.
McGraw also noted how each component failed—there was an arc flash in or near
the HV bushing, which also ruptured and broke the seal on the transformer; the
fuse failed to clear; and the copper ground wire ripped apart, melted, and vaporized
when exposed to voltage. McGraw explained that the ground system as designed
and installed was inadequate for the voltage and should have been stronger and
larger. While he otherwise did not specify what physical or mechanical defect
existed in the other components that failed to perform their functions, this makes
sense in light of his insistence that given the repeat problems, diagnostic testing
was necessary before a catastrophic event could occur. CenterPoint does not cite to
any evidence that specific mechanical or physical defects could have been
determined after the fire, the components having been damaged by both their
failures and the fire.
CenterPoint cites two cases in support of the proposition that it cannot be
assumed the transformer was defective merely because a fire occurred: Systech
Financial Corp. v. Vaughn, 558 S.W.2d 105, 105 (Tex. Civ. App.—Tyler, 1977),
and John R. Francis Building. Co. v. Bob Meador Co., 517 S.W.2d 693 (Tex. Civ.
App.—Houston [14th Dist.] 1974, no writ). In both of these cases, however, the
courts emphasized that there was no evidence establishing the cause of the fires
and instead the plaintiffs relied on a stacking of inferences in attempting to prove
the defendants’ negligence. Systech Fin., 558 S.W.2d at 105 (affirming directed
verdict where jury apparently concluded defendant started fire in his apartment
28
because he was a smoker); John R. Francis Bldg., 517 S.W.2d at 695 (holding that
although negligence could be proven by circumstantial evidence, mere surmise or
suspicion of negligence and a stacking of inferences was impermissible). In the
present case, as discussed in detail above, there was significant evidence, including
expert, video, and physical evidence, that the fire was started due to a failure of
CenterPoint’s equipment to properly function as a result of CenterPoint’s failure to
properly install, inspect, maintain, repair, and replace that equipment. The cited
cases are inapposite.
CenterPoint additionally argues that it presented conclusive evidence that the
equipment was not defective at the time of the fire because during the September 8,
2010 service calls, technicians replaced a couple of fuses and visually inspected
some of the components. In relation to this assertion, CenterPoint emphasizes a
portion of McGraw’s testimony where he denied that he was asserting the HV
bushing had a defect that technicians could have visually observed. CenterPoint
also points out that McGraw admitted the transformer’s core and coil remained
functional even after the fire.
These arguments, however, ignore a key component of McGraw’s
testimony—that CenterPoint breached the duty of care, at least in part, because its
technicians only performed a “cursory visual inspection” and failed to
diagnostically test the transformer and HV bushing. According to McGraw, visual
inspection was insufficient under the circumstances to discover the cause of the
repeat problems, and without determining the cause of the problems, CenterPoint
could not know how to remedy the issues. McGraw opined that simply replacing a
couple of components and then placing the equipment back into service was not
sufficient under the circumstances and violated the standard of care. He explained
that in order to determine the root problem or problems, CenterPoint needed to
29
conduct diagnostic testing, such as Megger testing, and without such testing,
CenterPoint would not know what to do to prevent further issues with the
equipment and a potentially catastrophic “whoops.”
CenterPoint’s point about the core and coil remaining functional is irrelevant
because McGraw acknowledged this in his testimony. He instead identified the HV
bushing—the entry point for high voltage electricity from the electrical distribution
system into the transformer—as the component that initially failed to contain the
current. McGraw explained that there was “more than enough . . . evidence that
there was a ground fault or a flashover on the top side of the transformer in and
around the high voltage bushing” so that a flashover occurred without
compromising the inside of the transformer. He further detailed that evidence and
described at length how he was able to eliminate other potential causes of the fire
such as the extension cords on the property. In short, McGraw’s testimony and the
evidence he cited in support was sufficient evidence that CenterPoint’s equipment
was defective or inadequate at a point when CenterPoint could and should have
discovered it.
Did CenterPoint negligently maintain the transformer? CenterPoint next
challenges the sufficiency of the evidence to prove that it negligently maintained
the transformer. As it did in its jurisdictional arguments discussed above,
CenterPoint begins this section of its brief by again misconstruing Coleman’s
theories as asserting CenterPoint negligently failed to (1) adopt a formal, proactive
maintenance program for its transformers and (2) provide all of its service
technicians with Megger devices and mandate the regular use of such devices in
maintaining its transformers. And again, CenterPoint does not cite to where
Coleman alleged either of these things. As set forth in detail above, McGraw
essentially testified that CenterPoint negligently designed and installed a ground
30
system that was inadequate for the voltage involved and failed to conduct
diagnostic testing in response to repeat problems with the same equipment so that
it could determine and correct the cause of those problems. To the extent relevant
to Coleman’s actual theories, we will address the rest of CenterPoint’s arguments.
CenterPoint notes that its technicians visually inspected the transformer
during the power outage about five weeks before the fire and asserts they
electrically tested the transformer when they restored power. As discussed above,
however, McGraw explained that a visual inspection was inadequate under the
circumstances, and CenterPoint does not cite any evidence that simply closing the
fuse and restoring power would provide the same information regarding potential
leakage currents or compromise to ground as would a Megger test or a “high
potential test” of the transformer and HV bushing. McGraw explicitly disagreed
that simply restoring power met the standard of care. CenterPoint also points out
that the technicians trimmed nearby trees to eliminate one possible cause of the
earlier power outage, but again, McGraw’s testimony clearly indicated this was
insufficient given the repeat problems the transformer had experienced.
Next, CenterPoint asks why they would have needed to determine the source
of the ground fault that caused the prior power outage when Coleman’s theory of
how the fire began concerns a failure of the system to contain an arc flash.
CenterPoint does not support this argument with further explanation or citation to
the record. The clear implication of McGraw’s testimony was that to meet the
standard of care, CenterPoint needed to have diagnostically tested the transformer
and HV bushing to ensure there was no leakage current or compromise to ground.
He explained that failure to do so and to determine and correct the cause of the
repeat problems most likely resulted in the fire. He additionally questioned the
adequacy of the ground system, which he also identified as a cause of the fire.
31
CenterPoint argues both that McGraw failed to expressly state CenterPoint
breached the standard of care by failing to conduct Megger testing and that he did
so but failed to explain why it was necessary. To be clear, McGraw explained that
diagnostic testing was required to meet the standard of care in order to determine
and correct the cause of the repeat problems with the equipment and prevent a
catastrophic “whoops” as occurred in this case. CenterPoint further notes McGraw
admitted he was unaware of any utility that mandated regular Megger testing of its
transformers. But McGraw did not assert CenterPoint was negligent for failing to
regularly Megger test transformers, he faulted CenterPoint for failing to conduct
diagnostic testing of the equipment under the circumstances of this case.
Lastly, CenterPoint cites Simmons v. Briggs Equipment Trust, 221 S.W.3d
109 (Tex. App.—Houston [1st Dist.] 2006, no pet.), for the undisputed proposition
that the mere occurrence of a fire does not give rise to a presumption of
negligence. After the plaintiff in Simmons was injured when a fire occurred in the
engine compartment of a rail car mover that he was operating, he sued the
company that was under contract to provide maintenance on the engine. Id. at 111.
In affirming a no-evidence summary judgment favoring the defendant, the court of
appeals explained that the mere fact that a ruptured hose was found in the engine
compartment after the fire only created a surmise or suspicion of negligence and
the plaintiff needed and failed to present expert testimony regarding the condition
of the hose, whether the maintenance company had violated the standard of care,
and what a reasonable maintenance company would have done under the
circumstances. Id. at 115. Here, as discussed in detail above, Coleman presented
expert testimony regarding the transformer and other equipment, that CenterPoint
violated the standard of care, and that a reasonable utility company would have
performed diagnostic testing on the equipment in response to the repeat problems
32
and would have installed an adequate ground grid in a dielectrically consistent
manner for the applied voltages. Nothing in Simmons suggests the evidence in the
present case was legally or factually insufficient.
CenterPoint has failed to establish that the evidence was legally or factually
insufficient to support the jury’s finding that CenterPoint breached a duty of care
owed to Coleman. Accordingly, we overrule CenterPoint’s second issue.
2. Proximate Cause
In its third issue, CenterPoint challenges the legal and factual sufficiency of
the evidence to establish that CenterPoint’s negligence proximately caused the fire.
To establish proximate cause, Coleman was required to establish both cause-in-fact
and foreseeability. See Lee Lewis Constr., Inc. v. Harrison, 70 S.W.3d 778, 784
(Tex. 2001). A plaintiff proves cause-in-fact by showing that the alleged act or
omission was a substantial factor in causing the injury without which the harm
would not have occurred. Id. Foreseeability means that the defendant should have
anticipated the danger that the alleged negligent act or omission created for others.
Id. at 785. 8
Here again, CenterPoint misconstrues Coleman’s theory of liability and
asserts that Coleman failed to offer evidence that a failure to (1) adopt a formal,
proactive maintenance program for its transformers and (2) provide all of its
service technicians with Megger devices and mandate the regular use of such
devices in maintaining its transformers caused the fire and resulting damages. We
8
The jury charge, which governs our analysis of the evidence, defined “proximate cause”
as meaning
a cause that was a substantial factor in bringing about an event, and without which
cause such event would not have occurred. In order to be a proximate cause, the
act or omission complained of must be such that an entity using ordinary care
would have foreseen that the event, or some similar event, might reasonably result
therefrom. There may be more than one proximate cause of an event.
33
will again address CenterPoint’s specific arguments to the extent relevant to
Coleman’s actual theory.
CenterPoint asserts that for evidence of cause-in-fact, Coleman relied
exclusively on conclusory statements by McGraw that properly maintaining the
transformer in some unspecified manner with some unspecified frequency would
have prevented the fire. In support, CenterPoint cites to some of McGraw’s more
general statements, for example, that had CenterPoint properly installed, inspected,
maintained, repaired, and replaced its equipment, the equipment most likely would
not have failed, and the fire would not have started. CenterPoint also cites to cases
in which courts held that expert testimony was insufficiently specific to establish
cause-in-fact. See Excel Corp. v. Apodaca, 81 S.W.3d 817, 821–22 (Tex. 2002);
Oncor Elec. Delivery Co., LLC v. S. Foods Grp., LLC, 444 S.W.3d 699, 712–13
(Tex. App.—Dallas 2014, no pet.); Goss v. Kellogg Brown & Root Inc., 232
S.W.3d 816, 819–20 (Tex. App.—Houston [14th Dist.] 2007, pet. denied). These
cases are distinguishable, however, because here, McGraw did not just make the
generalized statements regarding causation that CenterPoint cites but also offered
specific explanations of how CenterPoint’s failures were a substantial factor in
causing the fire and how the fire most likely would not have occurred if
CenterPoint had met the standard of care.
As discussed in more detail above, McGraw testified as to why and how
CenterPoint needed to diagnostically test the transformer and HV bushing for
leakage current or compromise to ground rather than just replacing a few
components and putting the transformer back into service in response to repeated
problems with the equipment. He indicated that doing so would have determined
the cause of the ground fault and informed CenterPoint what needed to be done to
remedy the issue. In regard to the ground system, he explained that it should have
34
been designed and installed in a dielectrically consistent manner for the voltages
applied and should have been larger and stronger than it was and had it been so, the
current would have been contained and the fire would not have occurred.
Evidence McGraw cited in support of his conclusions included the fire
marshal investigators’ report that largely supported his determination as to the
cause of the fire, the remains of the destroyed copper ground wire, the broken HV
bushing, the black carbon markings on the inside of the bushing and the
transformer tank, the fact that two gallons of oil were expelled from the
transformer, the bubbling pattern on the inside of the transformer tank, the video of
the start of the fire, and the testimony of CenterPoint’s technicians who stated that
they only performed a cursory visual inspection of the equipment, traded out a
couple of components, and trimmed some trees in response to the ground fault and
power outage five weeks before the fire but did not diagnostically test the
equipment because they did not have the tools to do so.
CenterPoint’s expert, Hautanen, asserted the copper wire simply melted
from the heat of the fire and the fire may have been caused by extension cords, but
both of these conclusions were rejected by McGraw and the investigators based on
the physical remains of the wire, the fact the fire would not have gotten hot enough
to melt copper, and the fact that the extension cord breakers had not cleared.
Although McGraw could have provided more details and specificity to help the
jury’s analysis, his testimony and supporting evidence was sufficient evidence of
cause-in-fact.
CenterPoint additionally points to a couple of isolated references in
McGraw’s testimony that it argues renders the evidence on causation insufficient.
The first comment came during the direct examination of McGraw when he was
asked what would have been required “to keep that transformer in good working
35
condition and prevent a fire” and McGraw began his response by saying, “I can't
speak to preventing the fire . . . .” Exactly what McGraw meant by that phrase is
unclear, but shortly after this remark, McGraw directly indicated that had
CenterPoint not breached the standard of care, the fire would not have occurred. As
sole judge of the weight and credibility of the testimony, the jury was free to
accept McGraw’s clear, direct statements and discount this one unclear phrase. See
Golden Eagle Archery, 116 S.W.3d at 761; Gator Gone Safety Pilots, 622 S.W.3d
at 537.
The second McGraw comment also came during his direct examination
when he acknowledged that “[e]verything fails. Everything ultimately fails. You
and I will both fail, right?” Again, it is not entirely clear what relevance the off-
hand remark has to the evidence of causation, and CenterPoint does not offer an
analysis. McGraw certainly did not and was not required to testify that the
equipment could not possibly have failed if maintained in proper condition. He
testified instead that had CenterPoint properly installed, inspected, maintained,
repaired, and replaced its equipment, the equipment most likely would not have
failed, and the fire would not have started. The jury was free to disregard the
remark.
The evidence was legally and factually sufficient to support the jury’s
finding that CenterPoint’s negligence was the proximate cause of Coleman’s
damages. We overrule CenterPoint’s third issue.
3. Lost Profits Damages
In its fourth issue, CenterPoint contends that Coleman failed to present
factually sufficient evidence to support the award of lost profits damages, even as
reduced by remittitur. Alternatively, CenterPoint contends the award was
excessive. As discussed above, the jury found lost profits damages in the amount
36
of $3,633,917, but the trial judge subsequently reduced this to $2,763,435. Under
this issue, CenterPoint seeks a new trial on both liability and damages. We will
begin by examining the law and evidence related to lost profits and then will turn
to CenterPoint’s specific arguments.
Governing law. Both sides agree that to recover lost profits damages,
Coleman was required to prove both the fact and amount of the loss by competent
evidence with reasonable certainty. See Horizon Health Corp. v. Acadia
Healthcare Co., Inc., 520 S.W.3d 848, 859 (Tex. 2017). Although evidence
sufficient to allow an exact calculation of lost profits is not required, lost profits
estimates must be based on objective facts, figures, or data from which the lost
profits may be ascertained. Id. Lost profits damages, however, may not be based on
evidence that is speculative, uncertain, contingent, or hypothetical. See Szczepanik
v. First S. Trust Co., 883 S.W.2d 648, 649 (Tex. 1994); Carter v. Steverson & Co.,
106 S.W.3d 161, 165 (Tex. App.—Houston [14th Dist.] 2003, pet. denied). When
evidence of damages is determined to be factually but not legally insufficient, a
remittitur or a new trial may be in order, depending on the state of the evidence.
See ERI Consulting Engineers, Inc. v. Swinnea, 318 S.W.3d 867, 880 (Tex. 2010).
The evidence. To prove lost profits, Coleman offered testimony from
himself, his wife, and his employees; tax returns and financial statements; and the
testimony of expert James Claywell, a CPA who specializes in business valuations
and lost profits calculations. Coleman and other witnesses described the
devastating effect the fire had on his car upholstery business. There was significant
evidence that the business lost established wholesale clients and saw a dramatic
and sustained loss of retail customers as a result of the fire. Prior to the fire,
Coleman had plans to expand his business by developing another property to
accommodate more business, and he had begun to put those plans into action,
37
having purchased a lot and had building plans drawn up. After the fire, those plans
were put on hold and Coleman struggled to obtain and pay for services related to
the development, including asphalt, plumbing, electricity, and building a
permanent structure. Coleman and his wife testified that the business was disrupted
for several years due to the fire and that the development of the other property took
several years longer than planned.
Claywell testified regarding his qualifications and his investigation into
Coleman’s business, including reviewing tax returns and financial statements,
corporate documents, marketing, and a narrative provided by Coleman and his
wife. To project what would have happened had there been no fire, Claywell used
“regression analysis,” which he described as a statistical analysis that looks at past
performance to project future expected performance. He said that according to the
Colemans’ narrative, they were “pretty much” completely out of the business for
two years, but Claywell said they subsequently discussed the business lag may
instead have been three years or as long as six years. Claywell explained that he
did not personally assess the length of business lag and it was an issue for company
management to decide and ultimately the jury. He noted, however, that two years
after the fire, a foreclosure and other difficulties were ongoing, suggesting the lag
was greater than two years.
Claywell identified important factors affecting his analysis, which included
that the company’s growth rate from 2007 until 2010 exceeded 31 percent
annually; given the growth rate and property available as collateral, Coleman could
have expected to qualify for a small business loan to begin developing the new
property in 2011; and it took until 2018 before they were finally able to open the
new building. Claywell calculated that if the business suffered a two-year business
lag, the lost profits would total $1,680,013 and if the business suffered a three-year
38
lag, the lost profits would be $2,763,435. He said that he did not specifically
calculate lost profits damages for a six-year lag, but he believed he had given the
jury enough information for that amount to be calculated. Claywell criticized the
analysis by CenterPoint’s expert, Jeffrey Compton, because Compton failed to take
the seasonality of the business into account; did not do “back transformations,”
which Claywell identified as a critical step in making lost profit calculations as
accurate as possible; and did not consider “step” or semi-variable costs.
On cross-examination, Claywell acknowledged that as time goes by, it
becomes more difficult to pin losses on a specific event. When pressed regarding
what business lag estimate was more reliable, Claywell testified that he would rely
on the two-year business lag because that was the estimate in the Coleman’s
written narrative and the period that they had originally thought it would be.
CenterPoint’s financial expert, Compton, calculated lost profits damages
based on a four-year business lag. He testified that he used two different methods
of calculations and came up with total damages of between $240,000 and
$300,000.
CenterPoint’s arguments. CenterPoint first hones in on Claywell’s
statement that he thought the two-year lag was the most supportable because it was
the period that the Coleman’s had originally proposed in their written narrative.
CenterPoint suggests that this comment rendered the evidence factually insufficient
to support the trial court’s award of $2,763,435, which according to Claywell, was
the estimated lost profit damages for a three-year lag. CenterPoint interprets
Claywell’s testimony as indicating he could not accept a three-year lag in keeping
with fair accounting practices. But that is not what Claywell said; while he
suggested he found the two-year lag more reliable, he did not say that the three-
year period was unacceptable or unreliable. Indeed, Claywell insisted he did not
39
personally analyze the length of the business lag and that it was an issue for
company management and ultimately the jury. He also noted that a foreclosure and
other ongoing difficulties suggested the lag was greater than two years. Although
Claywell based his comment regarding the two-year lag being more reliable on the
fact it was the period in the Colemans’ narrative, he also said that in later
discussions, the Colemans indicated the lag also could have been three years or as
long as six years. As mentioned above, CenterPoint’s expert found the business lag
to be four years and Coleman himself testified the business was disrupted for up to
eight years. CenterPoint offers no analysis of that testimony.
Neither the jury nor the court on remittitur was required to accept Claywell’s
suggestion that the two-year lag was more reliable. Claywell himself said that he
did not analyze the length of business lag, and Coleman offered other evidence
supporting a determination on the period of disruption. A jury is generally free to
accept or reject all or any portion of an expert’s testimony. Gator Gone Safety
Pilots, 622 S.W.3d at 537; see also McGailliard v. Kuhlmann, 722 S.W.2d 694,
697 (Tex. 1986) (explaining a jury has considerable discretion in evaluating
opinion testimony from an expert on the amount of damages). 9
CenterPoint next argues that the record does not contain objective facts,
figures, or data from which the lost profits may be ascertained. In particular,
CenterPoint argues that Coleman’s tax returns and financial records, which were
admitted at trial, do not by themselves support Claywell’s lost profits estimates.
However, while lost profits estimates must be based on objective facts, figures, or
9
CenterPoint cites Holland v. Hayden, 901 S.W.2d 763, 766 (Tex. App.–Houston [14th
Dist.] 1995, writ denied), for the proposition that lost profits damages cannot be based on the
subjective and conclusory testimony of the plaintiff alone. This proposition, however, has no
application in the present case where Coleman’s lost profits damages evidence included
substantial financial documentation, expert testimony, testimony from Coleman’s wife and
employees, in addition to testimony from Coleman himself.
40
data, see Horizon Health, 520 S.W.3d at 859, experts are not required to introduce
foundational data supporting their conclusions unless the opposing party or trial
court insists. See Tex. R. Evid. 705(a); Horizon Health, 520 S.W.3d at 865
(discussing rule in lost profits context); Arkoma Basin Expl. Co. v. FMF Assocs.
1990-A, Ltd., 249 S.W.3d 380, 389-90 (Tex. 2008) (citing Tex. R. Evid. 705(a) and
holding expert’s testimony was not unreliable, speculative, conclusory, or
insufficient to support the damages award merely because the foundational data
underlying his opinions and referenced in his testimony was not in the record).
Claywell’s testimony was far more involved than CenterPoint’s arguments
acknowledge. Claywell walked the jury in detail through his calculations using the
financial documents in the record as well as other financial information, his expert
report and supplemental report, and demonstrative exhibits that were not offered
into evidence. See Arkoma Basin, 249 S.W.3d at 389-90 (discussing expert’s use of
demonstrative exhibits).
Lastly, CenterPoint notes that its expert calculated total lost profits of
between $240,000 and $300,000. But, of course, the jury was free to accept
Claywell’s testimony over that of Compton. See Golden Eagle Archery, 116
S.W.3d at 761; Gator Gone Safety Pilots, 622 S.W.3d at 537.
The evidence was factually sufficient to support the trial court’s award of
$2,763,435 in lost profits damages. We overrule CenterPoint’s fourth issue.
C. Damage to Personal and Business Credit
In its fifth issue, CenterPoint contends that the trial court erred in overruling
its relevance objection to certain evidence offered by Coleman to prove past and
future damages to personal and business credit. CenterPoint does not seek a new
trial under this issue but, instead, argues that because this evidence was
inadmissible and was the only evidence Coleman presented in support of these
41
damages, the damages award should be reversed and a take nothing judgment
entered. The jury found and the trial court awarded $450,000 for past and $50,000
for future damage to personal and business credit.
The evidence CenterPoint cites is Coleman’s testimony regarding a house
that he owned that was foreclosed on and a boat that was apparently repossessed.
Coleman, however, cites in his brief a host of other evidence that was offered to
prove damages to personal and business credit, including, among other things,
evidence that Coleman’s credit score fell from the high 700s before the fire into the
400s afterwards; Coleman had purchased a lot, had building plans drawn up, and
expected to qualify for a small business loan before the fire but after the fire, it was
years later that his wife was able to get a loan to finance the new location; and
Coleman had to “max out” his credit cards after the fire, was unable to pay the
debt, and was sued by American Express.
Even in its reply brief, CenterPoint does not address this other evidence
except to assert that damage to a person’s credit rating is not recoverable as
damage to personal and business credit. We decline to construct CenterPoint’s
argument regarding the other evidence for it. See Tex. R. App. P. 38.1(i); Bhatia v.
Woodlands N. Houston Heart Ctr., PLLC, 396 S.W.3d 658, 666 (Tex. App.—
Houston [14th Dist.] 2013, pet. denied). We overrule the fifth issue.
II. Coleman’s Appeal
In a single issue in his appeal, Coleman asserts that the trial court erred in
remitting a portion of the damages found by the jury. As stated, the jury found lost
profits damages in the amount of $3,633,917, but the trial judge subsequently
reduced this amount to $2,763,435. We review a trial court’s order of remittitur
under a factual sufficiency standard. See Larson v. Cactus Util. Co., 730 S.W.2d
640, 641 (Tex. 1987); Carlton Energy Grp., LLC v. Phillips, 535 S.W.3d 542,
42
552–53 (Tex. App.—Houston [1st Dist.] 2016, pet. denied).
Coleman begins his argument by offering boilerplate law on lost profits
damages—which we discuss above under CenterPoint’s fourth issue—and then
listing alleged facts supported by a few citations to large, undifferentiated blocks of
testimony. The listed facts include much of that already discussed above regarding
lost profits, including expert Claywell’s testimony that his job was to provide
information from which the jury could then calculate damages, the annual growth
rate for the business before the fire was over 31 percent, and Coleman expected to
receive a business loan before the fire. Claywell provided specific lost profits
estimates based on two- and three-year business lags (respectively, $1,680,013 and
$2,763,435) but asserted he provided enough information for the jury to calculate
lost profits for six years if necessary. Coleman asserts CenterPoint’s expert
testified a four-year lag was accurate and Coleman and his wife testified in support
of business disruption lasting as long as eight years. Coleman particularly
emphasizes his own testimony regarding his credit score, plans, lost business after
the fire, and length of time it took to develop the new property.
After recounting the alleged facts in his brief, Coleman asserts that based on
the evidence, the jury could have reasonably concluded there was a two-, three-,
four-, five-, or six-year business lag. He then speculates that the jury found
“approximately 4 years” of business disruption and suggests the jury extrapolated
the lost profits figure it found from Claywell’s two and four-year calculations
along with the financial records.
Instead of offering any actual calculations in support of this speculation,
however, Coleman simply reports that this is what members of the jury said they
did after the trial. Coleman does not offer any proof of this claim. Even if we were
able to accept this claim regarding the jury’s rationale without proof, it does not
43
constitute evidence supporting the amount of lost profits damages found by the
jury. As discussed above, lost profits damages must be proven by competent
evidence with reasonable certainty. See Horizon Health Corp., 520 S.W.3d at 859.
Moreover, a party seeking lost profits damages must demonstrate one complete
calculation of lost profits. See ERI Consulting Engineers, 318 S.W.3d at 878; Univ.
Gen. Hosp., LP v. Prexus Health Consultants, LLC, 403 S.W.3d 547, 551 (Tex.
App.—Houston [14th Dist.] 2013, no pet.). And that calculation must be based on
net profits, not gross revenue or gross profits. Univ. Gen. Hosp., 403 S.W.3d at
551. Other than suggesting the jury could have done it, Coleman does not attempt
to show how the jury derived its figures with actual calculations. See Holt Atherton
Indus., Inc. v. Heine, 835 S.W.2d 80, 84–85 (Tex. 1992) (holding evidence was
insufficient because it did not provide indication of how plaintiff determined lost
profits damages).
Coleman has failed to establish that the trial court erred in ordering a
remittitur of lost profits damages. Accordingly, we overrule his sole cross-issue.
Conclusion
Having overruled all issues raised in CenterPoint’s appeal and Coleman’s
cross-appeal, we affirm the trial court’s judgment.
/s/ Frances Bourliot
Justice
Panel consists of Justices Wise, Jewell, and Bourliot.