FILED
United States Court of Appeals
PUBLISH Tenth Circuit
UNITED STATES COURT OF APPEALS October 27, 2020
Christopher M. Wolpert
FOR THE TENTH CIRCUIT Clerk of Court
_________________________________
EUGENE SCALIA, Secretary of Labor,
Petitioner/Cross-Respondent,
v. No. 19-9533
WYNNEWOOD REFINING CO., LLC;
Respondent/Cross-Petitioner,
and
OCCUPATIONAL SAFETY & HEALTH
REVIEW COMMISSION,
Respondent.
------------------------------
CORN REFINERS ASSOCIATION;
NATIONAL OILSEED PROCESSORS
ASSOCIATION; AMERICAN
CHEMISTRY COUNSEL; AMERICAN
FUEL & PETROCHEMICAL
MANUFACTURERS; AMERICAN
PETROLEUM INSTITUTE,
Amici Curiae.
–––––––––––––––––––––––––––––––––––
EUGENE SCALIA, Secretary of Labor,
No. 19-9578
Petitioner/Cross-Respondent,
v.
WYNNEWOOD REFINING CO., LLC;
Respondent/Cross-Petitioner,
and
OCCUPATIONAL SAFETY & HEALTH
REVIEW COMMISSION,
Respondent.
------------------------------
CORN REFINERS ASSOCIATION;
NATIONAL OILSEED PROCESSORS
ASSOCIATION; AMERICAN
CHEMISTRY COUNSEL; AMERICAN
FUEL & PETROCHEMICAL
MANUFACTURERS; AMERICAN
PETROLEUM INSTITUTE,
Amici Curiae.
_________________________________
Appeal from the Occupational Safety & Health Administration
(OSHA No. 13-0644)
_________________________________
Eric J. Conn and Micah R. Smith, Conn Maciel Carey LLP, Washington, D.C., for
Respondent/Cross-Petitioner.
Ronald J. Gottleib, Senior Trial Attorney, United States Department of Labor,
Washington, D.C. (Kate S. O’Scannlain, Solicitor of Labor, Edmund C. Baird, Associate
Solicitor of Labor for Occupational Safety and Health, Charles F. James, Counsel for
Appellate Litigation, United States Department of Labor, Washington, D.C., with him on
the briefs), for Petitioner/Cross-Respondent.*
Michele Schoeppe, American Chemistry Counsel, Washington, D.C.; Johnathan L. Snare
and Alana Genderson, Morgan Lewis & Bockius LLP, Washington D.C.; Richard
*
In an Order filed June 18, 2020, we granted the motion of Ronald J. Gottleib
to withdraw as counsel.
2
Moskowitz, American Fuel & Petrochemical Manufacturers, Washington, D.C.; and
Maryam Hatcher, American Petroleum Institute, Washington, D.C., filed an amicus
curiae brief on behalf of Respondent/Cross-Petitioner, for American Chemistry Counsel,
American Fuel & Petrochemical Manufacturers, and American Petroleum Institute.
James H. Hulme, Mark S. Dreux, and Alexandra M. Romero, Arent Fox LLP,
Washington, D.C., filed an amicus curiae brief on behalf of Respondent/Cross-Petitioner,
for the Corn Refiners Association and National Oilseed Processors Association.
_________________________________
Before BACHARACH, MURPHY, and MORITZ, Circuit Judges.
_________________________________
MORITZ, Circuit Judge.
_________________________________
After a boiler exploded at a refinery, the Occupational Safety and Health
Administration (OSHA) cited the refinery’s owner, Wynnewood Refining Co., LLC,
(Wynnewood or Wynnewood LLC), for violating 29 C.F.R. § 1910.119, which sets
forth requirements for the management of highly hazardous chemicals. The
Occupational Safety and Health Review Commission (the Commission) upheld the
violations. In doing so, it noted that the refinery had previously violated § 1910.119.
But it determined that these prior violations occurred before Wynnewood LLC owned
the refinery and that they therefore occurred under a different employer. Accordingly,
the Commission did not classify the violations as “repeat[] violations” under 29
U.S.C. § 666(a), which permits increased penalties for “employer[s] who willfully or
repeatedly violate[]” the regulation.
Wynnewood appeals from the Commission’s order, arguing that § 1910.119
does not apply to the boiler that exploded. Because we find that § 1910.119’s plain
text unambiguously applies to the boiler, we affirm the portion of the Commission’s
3
order upholding the violations. Secretary of Labor Eugene Scalia (the Secretary) also
appeals from the order, arguing that the Commission erred in failing to characterize
the violations as repeat violations. Because we agree with the Commission that
Wynnewood LLC is not the same employer as the refinery’s previous owner, we also
affirm the portion of the order concluding that these violations were not repeat
violations.
Background
Before December 2011, Wynnewood Inc., a subsidiary of Gary-Williams
Energy Corporation, owned the refinery. In December 2011, CVR Energy, Inc.,
(CVR Energy) “acquired all the stock of Gary-Williams Energy Corporation and its
subsidiaries, including Wynnewood, Inc.” App. vol. 21, 1145. After the purchase,
Wynnewood Inc. became Wynnewood LLC.
In September 2012, one of the refinery’s boilers—the Wickes boiler—
exploded after too much natural gas entered its firebox, which burns gas to heat the
boiler. As a result of the explosion, two employees died. Neither party asserts that the
Wickes boiler contains highly hazardous chemicals. But it is connected to two other
parts of the refinery that do—the fluid catalytic cracking unit (FCCU) and the
alkylation unit.
Shortly after the explosion, OSHA began an inspection of the refinery. After
investigating, OSHA cited Wynnewood for various violations of the Occupational
Safety and Health Act (OSH Act). Relevant here, these citations included violations
of § 1910.119, several of which OSHA characterized as repeat violations. An
4
administrative law judge (ALJ) affirmed all but one of these violations. But because
OSHA based its repeat-violations finding on violations that occurred under
Wynnewood Inc. and not Wynnewood LLC, the ALJ changed the characterization of
several of the violations from repeat to serious. The Commission affirmed the ALJ’s
decision.
Analysis
Both parties appeal the Commission’s decision. Wynnewood argues that the
regulation at issue does not apply to the Wickes boiler and that the Commission
therefore erred in affirming these violations. The Secretary argues that the
Commission erred by characterizing the violations as serious rather than repeat.
I. Application of § 1910.119 to the Wickes Boiler
Wynnewood argues that the regulation, which creates a standard for process
safety management (PSM) of highly hazardous chemicals, does not apply to the
Wickes boiler. The PSM regulation—which the parties also refer to as the PSM
standard—sets out “requirements [employers must follow] for preventing or
minimizing the consequences of catastrophic releases of toxic, reactive, flammable,
or explosive chemicals.” § 1910.119. The regulation applies only to “process[es]
which involve[]” a threshold amount of highly hazardous chemicals.
§ 1910.119(a)(1). And the regulation provides a specific definition of “process”:
Process means any activity involving a highly hazardous chemical
including any use, storage, manufacturing, handling, or the on-site
movement of such chemicals, or combination of these activities. For
purposes of this definition, any group of vessels which are
interconnected and separate vessels which are located such that a highly
5
hazardous chemical could be involved in a potential release shall be
considered a single process.
§ 1910.119(b).
Below, the Commission determined that the Wickes boiler could be part of a
process even though it did not contain any highly hazardous chemicals. The
Commission then analyzed the text of § 1910.119(b) and found that the Wickes boiler
was part of a process covered by the regulation—in other words, that it was part of a
“PSM-covered process” or was “PSM-covered”—for two independent reasons. App.
vol. 21, 1150. First, the Commission determined that the Wickes boiler was
interconnected with the FCCU and the alkylation unit, both of which are covered by
the PSM standard. Second, and alternatively, the Commission determined that the
Wickes boiler “was covered by the PSM standard because it was ‘located such that a
highly hazardous chemical could be involved in a potential release.’” Id. at 1152
(quoting § 1910.119(b)).
On appeal, Wynnewood argues that (1) the Wickes boiler was not
PSM-covered because it did not contain any highly hazardous chemicals, (2) the
Wickes boiler was not PSM-covered because of either its interconnection with or
location near a process, and (3) we should not defer to the Secretary because his new
interpretation deprived Wynnewood of fair notice. And, citing Kisor v. Wilkie,
Wynnewood urges us to interpret the regulation by examining its “text, structure,
history, and purpose,” even if the text of the regulation is unambiguous. 139 S. Ct.
2400, 2415 (2019).
6
At the outset, we note that Wynnewood’s proposed interpretive method rests
on a misunderstanding of Kisor. There, the Supreme Court emphasized that a
reviewing court should defer to an agency’s interpretation of its own regulations only
where the regulations are “genuinely ambiguous.” Id. at 2414. In doing so, the Court
reiterated that a reviewing court cannot conclude that a regulation is genuinely
ambiguous until after it thoroughly considers “the text, structure, history, and
purpose of a regulation.” Id. at 2415. But Kisor did not indicate that courts must
consider these sources before finding a statute unambiguous. Thus, nothing in Kisor
changes our longstanding approach to regulatory interpretation: begin with the text of
the regulation, and, if the meaning is clear, look no further. See Mitchell v. Comm’r,
775 F.3d 1243, 1249 (10th Cir. 2015); cf. Callahan v. U.S. Dep’t of Health & Human
Servs. Through Alex Azar II, 939 F.3d 1251, 1259 n.9, 1262 (11th Cir. 2019) (noting,
post-Kisor, that courts need not “consult extra[]textual evidence concerning ‘history’
and ‘purpose’” of regulation where “text is clear”; explaining that “Kisor itself
disclaims any groundbreaking”). And, post-Kisor, we have determined on at least
three occasions that a regulation was not ambiguous by relying on the text alone. See
Sierra Club v. EPA, 964 F.3d 882, 891 (10th Cir. 2020) (citing Kisor and concluding
that “regulation is not ambiguous” after analyzing only regulation’s text); In re MDL
2700 Genentech Herceptin (Trastuzumab) Mktg. & Sales Practice Litig., 960 F.3d
1210, 1234 (10th Cir. 2020) (citing Kisor and determining that “the regulatory
language resolves the question” of whether regulation is ambiguous); Reyes-Vargas
7
v. Barr, 958 F.3d 1295, 1306 (10th Cir. 2020) (citing Kisor and finding regulation
unambiguous based on only “plain language”).
Accordingly, when interpreting the PSM regulation, we “begin by examining
the plain language of the text, giving each word its ordinary and customary meaning.
If, after engaging in this textual analysis, the meaning of the regulation[] is clear, our
analysis is at an end, and we must enforce the regulation[] in accordance with [its]
plain meaning.” Mitchell, 775 F.3d at 1249 (internal citations omitted). If the
meaning of the text is not plain, then we must look to sources outside of the
regulation. Kisor, 139 S. Ct. at 2414. And if after “resort[ing] to all the standard tools
of interpretation” we find that the regulation is “genuinely ambiguous,” we may
apply Auer deference to OSHA’s interpretation of its regulation. Id. (discussing
deference owed to agency’s interpretation of its own regulation under Auer v.
Robbins, 519 U.S. 452 (1997)).
A. Whether the Wickes Boiler must Contain Highly Hazardous
Chemicals
With that understanding in mind, we return to Wynnewood’s arguments.
Recall that the PSM standard applies only to processes involving a threshold amount
of highly hazardous chemicals. § 1910.119(a)(1). And the term “process” is defined
in relevant part as “any activity involving a highly hazardous chemical” and includes
“any group of vessels which are interconnected and separate vessels which are
located such that a highly hazardous chemical could be involved in a potential
release.” § 1910.119(b) (emphasis added). Wynnewood first argues that the Wickes
8
boiler could not have been part of a process because it did not contain highly
hazardous chemicals. The Secretary agrees that the Wickes boiler does not contain
any highly hazardous chemicals, but he argues that “the presence of [a highly
hazardous chemical] in a vessel is not a precondition to coverage.” Aplee. Br. 39.
In making its argument, Wynnewood insists that the definition of process in
§ 1910.119(b) is ambiguous and urges us to rely on extratextual sources. Yet it
claims ambiguity by asserting that both it and the Secretary propose two different,
permissible interpretations of the text. Notably, Wynnewood never makes a
text-based argument for its interpretation of this aspect of the PSM standard. Instead,
in its opening brief, Wynnewood bases its interpretation on the regulation’s
preamble. And in its reply brief, Wynnewood “concede[s] the standard’s text does
not contain [the] explicit statement” that “all interconnected vessels must contain
[highly hazardous chemicals] to be considered part of a covered process,” and it
insists that “the purpose and structure of the standard imply it, and the history of the
standard demand it.” Aplt. Rep. Br. 34. But we do not consider extratextual sources if
the text is clear. Mitchell, 775 F.3d at 1249. Thus, we can’t reach Wynnewood’s
arguments before first considering whether the text of the regulation is ambiguous.
And so, we turn to the text of the regulation. Recall that the regulation
contains two sentences.1 The first sentence of the regulation defines process as “any
1
The dissent suggests that we should ignore the first sentence and “confine”
our analysis to the second sentence. Dissent 9. But the critical question before us is
whether the Wickes boiler is part of a PSM-covered process; thus, the first
sentence—defining what process means—is clearly relevant to this question. Indeed,
9
activity involving a highly hazardous chemical.” § 1910.119(b). Nothing on the face
of this definition requires a vessel to contain a highly hazardous chemical in order to
be part of a process. And its plain terms do not suggest that we should construe this
definition to apply to such a narrow category of vessels. Instead, its terms suggest the
opposite—the comprehensive phrase “any activity involving” captures a wide swath
of vessels in that they need only be part of an any activity that involves a highly
hazardous chemical. Thus, the definition of process unambiguously includes vessels
which do not contain a highly hazardous chemical. And because the text of the
regulation is unambiguous, we do not consider Wynnewood’s arguments based on
extratextual sources, including the preamble, and we conclude that the Wickes boiler
may be considered part of a process even though it did not contain any highly
hazardous chemicals. See Mitchell, 775 F.3d at 1249; cf. Peabody Twentymile
Mining, LLC v. Sec’y of Labor, 931 F.3d 992, 998 (10th Cir. 2019) (“Here, the
limitations that appear in the preamble do not appear in the language of the
regulation, and we refuse to engraft those limitations onto the language.”).2
the Commission began its analysis by reciting both sentences. Further, we note that
neither of the parties suggest we limit our consideration to only the second sentence.
Wynnewood does not meaningfully analyze either sentence because it fails to make a
text-based argument when discussing the PSM standard. The Secretary, for his part,
includes both sentences in his analysis. Additionally, he emphasizes that the first
sentence defines a process as “any activity involving a highly hazardous chemical.”
Aplee. Br. 27 (emphasis in original) (quoting § 1910.119). We therefore begin our
analysis with the first sentence.
2
The dissent considers extratextual sources like the preamble because it
concludes that the second sentence of the regulation “does not clearly say whether a
vessel can constitute part of a PSM process even when the vessel itself does not
contain any [highly hazardous chemicals].” Dissent 9. But this is not a genuine
10
B. Interconnection to PSM-Covered Units
Next, Wynnewood argues that the Commission erred by concluding that the
Wickes boiler was part of a process because it was interconnected to the
PSM-covered FCCU and alkylation unit. Wynnewood first asserts that a vessel
cannot be part of a process simply because it is interconnected to a PSM-covered
process. Instead, Wynnewood maintains, an interconnected vessel is not part of a
process unless it poses a risk of catastrophic release of highly hazardous chemicals.
With this argument, Wynnewood focuses on the second sentence of the
definition of process: “For purposes of this definition, any group of vessels which are
interconnected and separate vessels which are located such that a highly hazardous
chemical could be involved in a potential release shall be considered a single
process.” § 1910.119(b). Wynnewood argues that the requirement that vessels be
“located such that a highly hazardous chemical could be involved in the potential
release” applies to both “separate vessels” and to “vessels which are interconnected”
and that the text of the regulation supports its interpretation. Id. In doing so,
Wynnewood invokes the series-qualifier canon: “[W]hen there is a straightforward,
parallel construction that involves all nouns or verbs in a series, a prepositive or
postpositive modifier normally applies to the entire series.” Aplt. Rep. Br. 32
(quoting Antonin Scalia & Bryan A. Garner, Reading Law: The Interpretation of
ambiguity. Kisor, 139 S. Ct. at 2415. The plain text of the regulation does not require
a vessel to contain a highly hazardous chemical. Accordingly, we will not “wave the
ambiguity flag” to supplement an unambiguous text with an additional requirement.
Id.
11
Legal Texts 147 (2012)). Wynnewood then asserts that “any group of vessels which
are interconnected” and “separate vessels which are located” are two items in a series
that are both modified by “such that a highly hazardous chemical could be involved
in the potential release.”
But the series-qualifier canon does not support Wynnewood’s reading because,
here, there is no “straightforward, parallel construction” of items in a series. See
Potts v. Ctr. for Excellence in Higher Educ., Inc., 908 F.3d 610, 615 n.5 (10th Cir.
2018) (explaining that series-qualifier cannon does not apply “when the series is not
parallel”). To accept Wynnewood’s construction, we would have to treat the phrase
“such that a highly hazardous chemical could be involved in the potential release” as
a postpositive modifier. But doing so would require us to consider “separate vessels
which are located” as a standalone item in a series, and this phrase cannot
grammatically stand on its own as a separate item in the series. Thus, we find that the
text of the regulation is unambiguous: the phrase “such that a highly hazardous
chemical could be involved in the potential release” applies only to “vessels which
are located.” And therefore, the Commission did not err in concluding that the
Secretary need not demonstrate that the Wickes boiler posed a risk of catastrophic
release of highly hazardous chemicals in order to be part of a process. Rather, he
need only prove that the boiler was interconnected with a PSM-covered process.
And here, the Commission found that the Wickes boiler was interconnected to
the FCCU and alkylation unit, both of which are “PSM-covered processes by virtue
of the flammables contained in each.” App. vol. 21, 1150. In so doing, the
12
Commission noted that “the Wickes boiler is physically connected to both units
through [a] pipeline.” Id. Relying on dictionary definitions of “interconnect” and
“connect,” the Commission concluded that the “indirect, physical link between the
Wickes boiler and the [units] is sufficient for PSM coverage.” Id. at 1151. Although
Wynnewood attempts to challenge this conclusion it its reply brief, it fails to do so in
its opening brief. That is, in its opening brief, Wynnewood does not argue that the
Wickes boiler was not interconnected with the FCCU or alkylation unit or that the
Commission relied on the wrong definition of “interconnect.” Instead, Wynnewood’s
opening brief focused on the argument discussed earlier in this section—that is,
whether interconnected vessels must pose a risk of the release of highly hazardous
chemical. Thus, Wynnewood waived the argument that the Wickes boiler was not
interconnected with the PSM-covered FCCU and alkylation unit, and we uphold the
Commission’s decision on this point. See In re Motor Fuel Temperature Sales
Practices Litig., 872 F.3d 1094, 1113 n.5 (10th Cir. 2017) (“[A]rguments raised for
the first time in a reply brief are waived.”).
In sum, we conclude that the Wickes boiler can be part of a process as defined
in § 1910.119(b) even if it does not contain highly hazardous chemicals. We also
conclude that the Secretary was not required to demonstrate that the Wickes boiler
posed a risk of releasing a highly hazardous chemical in order to be part of a process
through interconnection. And Wynnewood waived its argument that the Wickes
boiler was not interconnected with a PSM-covered process. We therefore hold that
the text of the PSM regulation supports the Commission’s finding that the Wickes
13
boiler is part of a process covered by the regulation because it is interconnected with
the FCCU and the alkylation unit.3 Accordingly, we affirm the portion of the
Commission’s order upholding the PSM-standard violation.
II. Repeat Violation
The Secretary argues that the Commission erred in characterizing several of
Wynnewood’s violations as serious instead of repeat. The OSH Act increases
penalties for “[a]ny employer who . . . repeatedly violates” standards promulgated
under the Act. § 666(a). Repeat liability can apply to successor entities as long as
there is “‘substantial continuity’ between the two enterprises.” Sharon & Walter
Constr., Inc, 23 BL OSHC 1286, 1295 (No. 00-1402, 2010) (quoting Fall River
Dyeing & Finishing Corp. v. NLRB, 482 U.S. 27, 43 (1987)). Here, the Secretary
argues that for the purposes of § 666(a), the current iteration of Wynnewood—
Wynnewood LLC—is the same employer as Wynnewood Inc., which was the
refinery’s legal identity before its 2011 sale to CVR Energy. And therefore, the
Secretary continues, the Commission should have considered pre-2011 violations
when determining whether to characterize the violations at issue here as serious or
repeat.
3
Because we affirm the violations based on our conclusion that the Wickes
boiler was interconnected to a PSM-covered process, we need not reach
Wynnewood’s argument that the Commission erred in finding that the Wickes boiler
was part of a process because it was located “such that a highly hazardous chemical
could be involved in the potential release.” § 1910.119(b). And because our holding
is based on the text of the regulation rather than deference to the Secretary’s
interpretation, we need not reach Wynnewood’s arguments about why we should not
defer to the Secretary’s interpretation.
14
Below, the Commission determined that Wynnewood Inc. and Wynnewood
LLC were not the same employer and therefore declined to find repeat liability. In
reaching this conclusion, the Commission applied the three-factor
substantial-continuity test from Sharon & Walter. See Sharon & Walter, 23 BL
OSHC at 1295. In that case, the Commission determined that an employer can face
repeat liability even if the employer’s legal identity changes between the initial and
subsequent violations. Id. In doing so, Sharon & Walter adapted the substantial-
continuity test used in labor law. Id. at 1294–95. Under that adapted test, the
Commission considers the totality of the circumstances by analyzing three factors:
(1) “the nature of the business,” including the “continuity in the type of business,
products/services offered[,] and customers served” because “[s]uch continuity . . .
typically indicates that the nature of the activities associated with the business and
the inherent safety and health considerations are likewise unchanged”; (2) the “jobs
and working conditions . . . because of [their] close correlation with particular safety
and health hazards”; and (3) the “[c]ontinuity of the personnel,” focusing particularly
on “the personnel who specifically control decisions related to safety and health . . .
because the decisions of such personnel relate directly to the extent to which the
employer complies with the [OSH Act’s] requirements.” Id. at 1295.
Applying that test to the circumstances of the change of ownership between
Wynnewood Inc. and Wynnewood LLC, the Commission explained that the issue
“came down to the third category[,] given that the refinery’s business, product, jobs,
and working conditions were the same under both entities.” App. vol. 21, 1155. It
15
then noted that even though many supervisors at Wynnewood LLC remained the
same, new “high-level executives of Wynnewood LLC’s . . . parent company . . .
took an increased role in day-to-day operations at the refinery.” Id. at 1155–56. And
it found that the Wynnewood LLC supervisors did not control the refinery’s safety
policy. Id. Instead, it found that “these managers merely implemented the safety
policies set by the previous parent company and then CVR Energy.” Id. at 1156 n.13.
The Commission further recognized that the “new management focuse[d] on
improving safety, health, and the proper implementation of [the] PSM [standard]”
and that it made substantial investments in safety personnel and equipment, resulting
in a “safety culture shift.” Id. at 1156. Based on these facts, the Commission
concluded that there was not a continuity in personnel and that therefore Wynnewood
LLC was not a successor of Wynnewood Inc.
On appeal, the Secretary argues that (1) the Commission legally erred by
incorrectly applying the substantial-continuity test and (2) even assuming it correctly
applied the test, the Commission nevertheless factually erred by concluding that the
third factor, continuity of personnel, favored successor liability. We consider each
argument in turn.
A. Application of the Substantial-Continuity Test
The parties agree that the substantial-continuity test applies.4 But they disagree
on whether the Commission correctly applied that test. The Secretary argues that the
4
Wynnewood alternatively argues that we should apply an alter-ego test,
explaining that, in practice, the substantial-continuity test operates like the alter-ego
16
Commission did not correctly apply the substantial-continuity test because it
(1) failed to consider the totality of the circumstances and (2) considered irrelevant
evidence. As it is a question of law, we review de novo whether the Commission
incorrectly applied the substantial-continuity test. Trimmer v. U.S. Dep’t of Labor,
174 F.3d 1098, 1102 (10th Cir. 1999).
As the Secretary explains, the substantial-continuity test considers the totality
of the circumstances across the three factors. See Sharon & Walter, Inc., 23 BL
OSHC at 1295. The Secretary argues that the Commission displaced the totality-of-
the-circumstances analysis by requiring each of the three factors to favor successor
liability instead of “evaluat[ing] all of the evidence and explain[ing] why” it weighed
the factors as it did. Aplee. Rep. Br. 7 n.2. And he argues that “even if one or more
factors does not weigh in favor of successor liability[,] the ‘totality of the
circumstances’ can still establish” successor liability. Aplee. Br. 60 (quoting Fall
River Dyeing & Finishing Corp., 482 U.S. at 43). Likewise, the dissent contends that
we can’t affirm the Commission’s analysis because the Commission “never explained
why the third factor would override the other two.” Dissent 20. But the Commission
correctly explained the substantial-continuity test, never indicating that the test
required continuity across all three factors. Instead, when considering the evidence in
light of the three factors, the Commission explained how the change in personnel
test. But in Sharon & Walter, the Secretary made an alter-ego argument to the
Commission, and the Commission instead chose to apply the substantial-continuity
test. See Sharon & Walter, Inc., 23 BL OSHC at 1296 n.17. We therefore decline to
apply the alter-ego test here.
17
directly impacted the safety of the refinery, thus demonstrating why it weighed that
factor so heavily. Indeed, the Commission acknowledged that even though the first
two factors favored a repeat violation, substantial evidence as to the third factor
demonstrated that the “changeover in ownership resulted in changes in management
practices, procedures, and culture significant enough to break the chain of liability
stemming from Wynnewood Inc.’s previous actions.” App. vol. 21, 1156 n.13.5 We
therefore reject the Secretary’s argument that the Commission failed to consider the
totality of the circumstances.
Next, the Secretary argues that the Commission deviated from the substantial-
continuity test by considering irrelevant factors.6 First, the Secretary asserts—and the
5
The dissent further argues that the Commission inappropriately considered
this change in culture and safety policies. In doing so, the dissent proposes that we
limit our analysis of the third factor to determining “whether the employees
addressing safety were the same in both the old and new entities.” Dissent 21. But the
Commission appropriately criticized this “rote application” of the third factor as
“paint[ing] an inaccurate picture of how safety policy was set and how safety
decisions were made at the refinery.” App. vol. 21, 1156 n.13. And this criticism is
consistent with Sharon & Walter, which explained that the rationale underpinning the
third factor was that certain personnel “control decisions related to safety and
health”—thus suggesting that this factor permits consideration of whether health and
safety decisions remained the same, not simply whether personnel remained the
same. 23 BL OSHC at 1295 (emphasis added).
6
In his opening brief, the Secretary suggests that the Commission relied on
another type of irrelevant consideration: change in the parent company’s personnel as
opposed to Wynnewood’s. However, in his reply brief, he clarifies that he does not
argue that “no consideration can be given to changes in management at the corporate
parent” but that instead such considerations were inappropriate given the facts of this
case. Aplee. Rep. Br. 13. Thus, this argument concerns whether the Commission
came to the correct conclusion, not whether the Commission correctly applied the
substantial-continuity test. Accordingly, we do not address this argument here, where
we determine whether the Commission correctly applied the substantial-continuity
test.
18
dissent agrees—that the Commission erroneously relied on the fact that Wynnewood
did not change its legal identity to avoid a repeat characterization. And it argues that
a company’s motive is not part of the three-factor test articulated in Sharon &
Walter. See 23 BL OSHC at 1295. But the Commission did not incorporate
Wynnewood’s motive into its analysis of the three factors—instead, the Commission
mentioned Wynnewood’s motive only after it analyzed the various factors and
concluded that there was no substantial continuity. Because it was “not necessarily
involved nor essential to determination of the case,” this statement was dicta. Tuttle
v. United States (In re Tuttle), 291 F.3d 1238, 1242 (10th Cir. 2002) (quoting
Rohrbaugh v. Celotex Corp., 53 F.3d 1181, 1184 (10th Cir. 1995)). Moreover, the
Commission explained in Sharon & Walter that if it were to “to restrict a repeat
characterization to the legally identical employing entity, [an employer] could
successfully avoid a repeat characterization for future violations by simply changing
its legal identity.” 23 BL OSHC at 1293. Thus, a concern about motive animated the
Commission’s decision in Sharon & Walter, even if the Commission did not
incorporate that concern into the final test adopted in that case. And the
Commission’s dicta here merely emphasizes that its conclusion was consistent with
that underlying concern; it does not indicate that the Commission misapplied the
substantial-continuity test.
The Secretary further argues that the Commission “rest[ed its decision] on the
misguided notion that it would be unfair or inequitable to assess heightened penalties
against Wynnewood LLC based on safety lapses of its predecessor.” Aplee Br. 69.
19
But the statement the Secretary cites to support this assertion—“[W]e find these are
not the appropriate circumstances to affirm a repeat characterization”—doesn’t bear
the weight of his argument. Id. (alteration in original) (quoting App. vol. 21, 1156).
In the paragraphs prior to this statement, the Commission analyzed the three Sharon
& Walter factors, and it preceded this statement with the phrase “[i]n light of the
foregoing.” App. vol. 21, 1156. Thus, it is clear that when the Commission referred
to the “appropriate circumstances,” it was referring to its analysis of the Sharon &
Walter factors. Accordingly, we reject the Secretary’s argument that the Commission
relied on irrelevant information. Because we also reject the Secretary’s totality-of-
the-circumstances argument, we conclude that the Commission did not legally err by
misapplying the substantial-continuity test.
B. Substantial Evidence
We now turn to the Secretary’s argument that even if the Commission did not
legally err by incorrectly applying the substantial-continuity test, it nevertheless
factually erred by failing to find that the third factor, continuity of personnel, favors
successor liability. Below, the Commission found that the continuity-of-personnel
factor did not support finding substantial continuity. In doing so, it noted that
“several of the day-to-day managers were in the same positions under Wynnewood
Inc. and Wynnewood LLC.” App. vol. 21, 1155. But it explained that high-level
executives at CVR Energy “took an increased role in day-to-day operations at the
refinery.” Id. at 1156. It found that these executives “focused on improving safety,
health, and the proper implementation of [the PSM standard].” Id. As a result, the
20
refinery’s “safety culture shift[ed].” Id. Based on this analysis, the Commission
found that there was no substantial continuity between Wynnewood Inc. and
Wynnewood LLC.
In reviewing this finding, we note that the substantial-continuity test “is
primarily factual in nature.” Fall River Dyeing & Finishing Corp., 482 U.S. at 43;
see also Sharon & Walter, Inc., 23 BL OSHC at 1296 (favorably citing Fall River for
this point). We review the Commission’s factual findings “under a substantial[-]
evidence standard, which is satisfied if ‘“a reasonable mind” would consider the
evidence adequate to support the conclusion reached.’” Jake’s Fireworks Inc. v.
Acosta, 893 F.3d 1248, 1257 (10th Cir. 2018) (quoting Universal Const. Co. v.
Occupational Safety & Health Rev. Comm’n, 182 F.3d 726, 732 (10th Cir. 1999)). In
making this determination, “[w]e do not reweigh the evidence, second-guess the
factual inferences drawn therefrom, or substitute our judgment on the credibility of
witnesses.” Id. And we “must affirm a Commission determination supported by
substantial evidence even though we might reach a contrary result in a proceeding de
novo.” CCI, Inc. v. Occupational Safety & Health Rev. Comm’n, 688 F.2d 88, 89
(10th Cir. 1982).
In attempting to show that the Commission’s decision lacked substantial
evidence, the Secretary first argues that the Commission inappropriately relied on the
change in personnel of Wynnewood’s parent company, CVR Energy. The Secretary
suggests that “Sharon & Walter did not place significance on the policy-making
authority of executives.” Aplee. Br. 68. Thus, the Secretary reasons, the Commission
21
should not have relied upon the change in executive personnel in concluding there
was no continuity of personnel. In doing so, he relies on United Food & Commercial
Workers International Union, AFL-CIO, Local 152 v. NLRB, 768 F.2d 1463 (D.C.
Cir. 1985). There, the D.C. Circuit found that although a “change in upper level
personnel occurred,” the NLRB erred in concluding that there was substantial
continuity between two employers. United Food, 768 F.2d at 1473. Specifically, the
court found “no substantial evidence to support the [NLRB’s] apparent conclusion
that the upper[-]level[-]personnel changes effected any substantial transformation in
[workplace] operations.” Id.
Here, by contrast, the Commission found that CVR Energy executives
controlled safety-related decisions and, as a “direct result,” “the safety policies at the
refinery changed significantly.” App. vol. 21, 1156 n.14. And substantial evidence
supports this finding. For example, the operations manager at the time testified that,
“as a result of the purchase by CVR Energy,” Wynnewood “went through some
pretty drastic changes” related to safety, including hiring two new members of its
safety personnel. App. vol. 1, 1714. He also testified that “the corporate management
[was] very active, involved every day,” and that CVR Energy permitted “access to
capital or to funds” for safety, which were “previous[ly] very difficult” to access. Id.
at 1714, 1716. The process-safety manager indicated that CVR Energy “raised the
level of the safety programs” and that its “involvement in the safety program
included process safety.” Id. at 1625. And a safety specialist testified that CVR
Energy executives made the “budget for safety . . . pretty open” and “review[ed,]
22
revis[ed, and] train[ed] on safety policies [and] on safety procedures.” Id. at 2147.
Thus, by considering the involvement of CVR Energy executives, the Commission
focused on the “[c]ontinuity of the personnel who specifically control decisions
related to safety and health,” as required by Sharon & Walter. 23 BL OSHC at 1295.
The Secretary next argues that the Commission ignored the continuity of
several refinery supervisors between Wynnewood Inc. and Wynnewood LLC. But the
Commission did not ignore the continuity of these supervisors; instead, it found that
“safety policy at the refinery was not controlled by these managers” and that they
“merely implemented the safety policies set by the previous parent company and then
by CVR Energy.” App. vol. 21, 1156 n.14 (emphasis omitted). To be sure, there is
evidence that these supervisors were involved in establishing procedures for using
the Wickes boiler. But, as noted above, there is also evidence supporting the
Commission’s conclusion that the CVR Energy executives controlled the safety-
related decisions. And when reviewing the Commission’s decision for substantial
evidence, it is not our role to “reweigh the evidence [or] second-guess the factual
inferences drawn therefrom.” Jake’s Fireworks Inc., 893 F.3d at 1257. We thus
conclude that substantial evidence supports the Commission’s analysis of the
involvement of the CVR Energy executives.
Finally, the Secretary argues that we should not consider changes in safety
policy because such changes relate to working conditions and the Commission found
that the working conditions were the same between the two entities. True, the
Commission did indicate that the working conditions under Wynnewood Inc. and
23
Wynnewood LLC were “the same.” App. vol. 21, 1155. But the Commission also
emphasized Wynnewood LLC’s safety-related changes at the refinery and, as
discussed, those changes were initiated by CVR Energy executives. For example, the
Commission credited the “more formalized training programs,” the “$130 million in
equipment upgrades,” and the “safety culture shift at the refinery.” Id. at 1157.
We are not convinced that such changes are better classified as changes to
working conditions. And even if we accepted this categorization, the Secretary cites
no authority indicating that the Commission’s decision to consider the changes under
one category rather than another means that we must disregard this evidence on
appeal. Cf. Jake’s Fireworks Inc., 893 F.3d at 1257 (explaining that the substantial-
evidence standard “is satisfied if ‘“a reasonable mind” would consider the evidence
adequate to support the conclusion reached’” (quoting Universal Const. Co., 182
F.3d at 732 )). Moreover, Sharon & Walter emphasized the continuity of “personnel
who specifically control decisions related to safety and health” because “safety-
related decisions made by managers and supervisors” impact the “type and extent of
workplace hazards.” 23 BL OSHC at 1295. Accordingly, substantial continuity
depends in part on the continuity of personnel who make decisions that could impact
workplace hazards. Id.
Thus, we find that substantial evidence supports the Commission’s finding that
there was no substantial continuity between Wynnewood Inc. and Wynnewood LLC.
Accordingly, we affirm the Commission’s decision to characterize the violations at
issue as serious rather than repeat.
24
Conclusion
Because the Wickes boiler was part of a PSM-covered process, we affirm the
PSM-standard violations. And because the Commission correctly applied the
substantial-continuity test and substantial evidence supports its finding that
Wynnewood Inc. and Wynnewood LLC were not the same employer, we affirm the
characterization of violations as serious rather than repeat.
25
Eugene Scalia, Secretary of Labor v. Wynnewood Refining Co., L.L.C,
et al., Nos. 19-9533, 19-9578
BACHARACH, J., dissenting.
In 2012, a boiler at Wynnewood’s refinery exploded, killing two
employees. (The boiler is pictured here shortly after the explosion.)
The Secretary of Labor investigated and cited Wynnewood for twelve
regulatory violations, eleven involving the boiler. The Secretary
characterized five of the twelve violations as “repeat,” triggering
heightened penalties.
The Occupational Safety and Health Review Commission upheld the
citations involving the boiler. But the Commission rejected the Secretary’s
characterization of the violations as “repeat,” reasoning that the previous
violations had taken place when a different entity had owned the refinery.
Both parties have appealed.
Wynnewood’s appeal focuses on the eleven citations involving the
boiler. Though the facts are largely undisputed, the parties disagree about
the application of regulations known as the “Process Safety Management”
(PSM) standard. The Secretary adopted these regulations to prevent and
minimize the impacts of catastrophic chemical releases, imposing stringent
requirements for employers to enhance safety. See 29 C.F.R. § 1910.119;
R., vol. I, at 1214–15 (testimony by the Secretary’s designated
representative). 1
In appealing, Wynnewood argues that the PSM standard doesn’t
apply to the boiler. The majority rejects this argument, concluding that the
PSM standard applies because the boiler was connected to other vessels
containing highly hazardous chemicals (HHCs).
The Secretary’s appeal involves the applicability of heightened
penalties for employers who commit repeat violations. When the previous
violations were committed, the refinery was owned by a separate legal
1
When the PSM standard doesn’t apply, other regulations may apply.
The employer’s duties may vary based on the applicability of particular
regulations. See Teal v. E.I. DuPont de Nemours & Co., 728 F.2d 799, 804
(6th Cir. 1984).
2
entity. Though the owner’s legal entity changed, the Secretary argues that
the new entity is substantially the same as the old one and should be
regarded as the same entity. The Commission rejected this argument,
concluding that the new entity differs from its predecessor. The majority
agrees with the Commission.
I respectfully disagree with the majority in both appeals.
First, I agree with Wynnewood that the Secretary hasn’t shown that
the PSM standard applies to the boiler. In deciding the applicability of the
PSM standard, we’re confined to the regulatory provision invoked by the
Secretary and the Commission. Both relied solely on a provision that
unambiguously encompasses only vessels that contain an HHC. But the
boiler itself contained no HHC, so I would vacate the eleven violations
involving the boiler.
Second, I agree with the Secretary in his appeal regarding the
applicability of heightened penalties for repeat violations. For the twelfth
citation, the Commission misapplied the legal test for determining whether
the entity itself has changed after a change in ownership. So I would
remand for the Commission to reconsider the applicability of heightened
penalties for the twelfth citation.
3
I. The Secretary and the Commission relied on a provision that
unambiguously applies only to vessels containing HHC.
The Secretary and the Commission relied on a regulation, 29 C.F.R.
§ 1910.119, which regulates vessels constituting part of a covered
“process.” We must ask: Does the boiler constitute part of a “process”
covered by the PSM standard? The Commission answered “yes,” and the
majority agrees. I do not. The Commission relied on a provision in the
PSM standard that applied only if the boiler contained at least some HHC.
The boiler didn’t, so the PSM standard didn’t apply. 2
A. We apply deferential review of the Secretary’s regulatory
interpretation only if the regulation is ambiguous.
When reviewing the Secretary’s regulatory interpretation, we apply
deference under the scheme described in Kisor v. Wilkie, ___ U.S. ___, 139
S. Ct. 2400 (2019). Under Kisor, however, courts should defer to an
agency’s interpretation only if the regulation is genuinely ambiguous.
Kisor, 139 S. Ct. at 2414. In determining whether a regulation is
2
Wynnewood also argues that the PSM standard doesn’t apply to the
boiler because
a risk of catastrophic release must exist for interconnected
vessels and
the Secretary must prove a “reasonable probability” that the
vessel could contribute to a catastrophic release.
I would not reach these issues.
4
ambiguous, we “must exhaust all the ‘traditional tools’ of construction,”
including the regulatory text, structure, history, and purpose. Id. at 2415
(quoting Chevron U.S.A. Inc. v. Nat. Res. Def. Council, Inc., 467 U.S. 837,
843 n.9 (1984)).
B. The applicability of the PSM standard turns on two
sentences in the regulatory definition of “process.”
The PSM standard defines “process” in two sentences. The first
sentence states that “process” is “any activity involving [an HHC]
including any use, storage, manufacturing, handling, or the on-site
movement of such chemicals, or combination of these activities.” 29 C.F.R.
§ 1910.119(b). The second sentence explains what constitutes a single
process: “For purposes of this definition, any group of vessels which are
interconnected and separate vessels which are located such that a highly
hazardous chemical could be involved in a potential release shall be
considered a single process.” Id.
The two sentences reflect two ways that a vessel can constitute part
of a single PSM “process”:
1. if the vessel is used in an “activity” involving an HHC or
2. if a group of vessels is “interconnected” or “located such that
[an HHC] could be involved in a potential release.”
Id.
The first sentence focuses on particular activities involving an HHC.
For example, if the boiler had constituted equipment used to store or move
5
HHCs, a process would exist under the first sentence. 29 C.F.R.
§ 1910.119(b). And if that process involved enough HHC, the PSM
standard would apply. 29 C.F.R. § 1910.119(a)(1). If the first sentence had
triggered the PSM standard, the boiler would constitute “process
equipment.”
The second sentence focuses on the interconnection with or
proximity to other equipment. In my view, the second sentence governs the
applicability of the PSM standard to Wynnewood’s boiler.
C. The Secretary and the Commission relied solely on the
second sentence of the PSM standard’s definition of
“process.”
In considering the boiler part of a PSM process based on
interconnection with or proximity to other equipment, the Secretary and
Commission relied solely on the second sentence of the definition of
“process.” See, e.g., R., vol. XXI, at 454–56 (the Secretary’s Post-Hearing
Brief, relying on the second sentence for the applicability of the PSM
standard); R., vol. I, at 785 (the Secretary’s statement that his theory of
PSM coverage had “always” been interconnection with or proximity to
other vessels), 1221 (testimony by the Secretary’s designated
representative, agreeing that he had “determined that the boiler was a
covered process because it was interconnected”), 1237 (further testimony
6
by the designated representative that his other theory of coverage entailed
proximity to a covered process). 3
Though the Secretary and Commission relied solely on the second
sentence for the regulatory definition of “process,” the majority relies on
the first sentence. According to the majority, Wynnewood frames its
arguments around the first sentence. See Majority Op. at 8 (“Wynnewood
first argues that the Wickes boiler could not have been part of any such
activity . . . .”). But Wynnewood has consistently focused on the second
sentence, not the first one. See R., vol. I, at 91 (arguing about the
applicability of the PSM standard based on “interconnection” rather than
the existence of a “process activity”); Appellant’s Opening Br. 11
(Wynnewood’s summary of its argument about the PSM standard, quoting
only the second sentence). Wynnewood’s focus is understandable given the
Secretary and Commission’s reliance on the second sentence.
The difference is decisive. The parties agree that the first sentence
covers Wynnewood’s fluid catalytic cracking unit and alkylation unit
because they contain HHCs. If the boiler had been used in a process with
the fluid catalytic cracking unit or alkylation unit, the boiler would be
subject to the PSM standard as a PSM “activity” under the first sentence.
3
The designated representative testified that he was the agency’s
representative who had decided that the PSM standard applied to the
boiler. R., vol. I, at 1105–06.
7
But the Commission didn’t find that the boiler had been used in a
PSM activity. The Commission instead applied the PSM standard based on
the boiler’s interconnection with or proximity to two other vessels (the
fluid catalytic cracking unit and alkylation unit). Interconnection or
proximity of vessels could trigger the PSM standard only under the
“process” definition’s second sentence, not the first sentence.
The distinction is evident in the Commission’s order. The
administrative law judge had concluded that the boiler was covered as a
PSM “activity,” relying heavily on an administrative precedent (Delek
Refining, Ltd.) that had focused on whether a piece of equipment was part
of a covered activity. Delek Refining, Ltd., 25 BNA OSHC 1365 (No. 08-
1386, 2015), 2015 WL 1957889 at *7, aff’d in relevant part, 845 F.3d 170
(5th Cir. 2016). Delek had examined “the ‘activity’ involving” the covered
process, concluding that the equipment was “part of a ‘process’ covered by
the PSM standard because [the equipment was] an integral part of the
‘manufacturing, handling [and] on-site movement of [highly hazardous
chemicals].” Id. (quoting the first sentence of the “process” definition in
29 C.F.R. § 1910.119(b)). Delek thus rested on the first sentence of the
regulatory definition of “process.”
But the Commission rejected the administrative law judge’s reliance
on Delek, explaining that even though “Delek did address the PSM
standard’s ‘process’ definition, it focused on the first sentence and whether
8
the positive pressurization unit was involved in the ‘manufacturing,
handling [and] on-site movement’ of HHCs . . . not whether vessels were
interconnected pursuant to the definition’s second sentence.”
Commission’s Order at 9 (emphases added). So the Commission focused
solely on the second sentence, rejecting the administrative law judge’s
reliance on the first sentence. Id. at 9–10.
Given the Commission’s reliance on the second sentence, I would
confine our review to the Commission’s reasoning. See Indus. Union Dep’t
v. Am. Petroleum Inst., 448 U.S. 607, 631 n.31 (1980) (“[T]he validity of
an agency’s determination must be judged on the basis of the agency’s
stated reasons for making that determination.”).
D. The text of the second sentence is ambiguous without
considering the regulatory preamble.
Wynnewood argues that the second sentence refers only to
interconnected and co-located vessels that contain an HHC. To assess that
argument, we apply the traditional tools of construction to the text of the
regulation. Kisor, 139 S. Ct. at 2415.
Viewed in isolation, the second sentence does not clearly say whether
a vessel can constitute part of a PSM process even when the vessel itself
does not contain any HHC. The second sentence refers to “any group of
vessels,” 29 C.F.R. § 1910.119(b), but the PSM standard doesn’t define
“vessels.” So we must consider not only the regulatory text but also the
9
interpretive tools involving the regulatory structure, history, and purpose.
See pp. 4–5, above. These interpretive tools include the preamble, which
shows that interconnection with or proximity to another vessel can trigger
the PSM standard only if both vessels contain HHC.
E. The preamble shows that the second sentence covers vessels
only if they contain an HHC.
The parties debate the value of the preamble in interpreting the PSM
definition of “process.” Given the apparent ambiguity in this definition, we
must consider the regulatory history and purpose. Kisor, 139 S. Ct. at
2415; see pp. 4–5, above. To consider the history and purpose, we may
focus on the preamble if it does not override the plain text of a provision:
Some courts and commentators have said that the prologue
cannot be invoked when the text is clear. This limitation is
reasonable if it means that the prologue cannot give words and
phrases of the dispositive text itself a meaning that they cannot
bear. But . . . [i]f the prologue is indeed an appropriate guide to
meaning, it ought to be considered along with all other factors
in determining whether the instrument is clear. The factors
undermining its reliability affect its weight, not its relevance.
Antonin Scalia & Bryan A. Garner, Reading Law: The Interpretation of
Legal Texts 218 (2012) (footnote omitted; emphasis in original); see
Majority Op. at 7–8.
The preamble shows that the Secretary added the second sentence to
clarify when multiple vessels containing HHCs would constitute a single
process:
10
[A] new sentence has been added to clarify the fact that
interconnected and nearby vessels containing a highly
hazardous chemical would be considered part of a single process
and the quantities of the chemical would be aggregated to
determine if the threshold quantity of the chemical is exceeded.
Process Safety Management of Highly Hazardous Chemicals; Explosives
and Blasting Agents, 57 Fed. Reg. 6356, 6372 (Feb. 24, 1992) (emphasis
added). The preamble thus focuses on vessels “containing” an HHC. So the
Secretary explained in the preamble that the agency would measure the
quantity of HHC by combining the HHCs in each vessel:
The boundaries of a “process” would extend to quantities
. . . which are interconnected and would include separate vessels
located such that . . . an event such as an explosion would affect
interconnected and nearby unconnected vessels which contain
quantities of the chemical that when added together would
exceed the threshold quantity . . . .
57 Fed. Reg. at 6372 (emphasis added). 4 Given this explanation, the second
sentence unambiguously applies only when HHCs exist in the
interconnected or nearby vessels.
4
The agency also reflected its focus in guidance materials published
soon after adoption of the PSM standard. In these materials, the agency
addressed the definition of the phrase “aggregate threshold quantities.”
The agency explained:
In accordance with the second sentence of the definition of
“process,” quantities of a particular hazardous chemical
contained in vessels that are interconnected—and in unconnected
vessels that may be adversely affected due to an incident at a
nearby process—must be combined to determine whether the
threshold level of a hazardous chemical has been reached.
11
F. The Secretary’s designated representative testified that the
second sentence applies to an interconnected or nearby
vessel only if it contains HHC.
At the hearing before the administrative law judge, the Secretary’s
designated representative (Mr. Rick Hartung) testified. He acknowledged
that he was the agency representative who had decided that the PSM
standard applied to the boiler. See p. 7 n.3, above. In explaining that
decision, he admitted that under the second sentence, the PSM standard
would apply to the boiler only if it contained HHC:
Q. It says, “For purposes of this definition, any group of
vessels which are interconnected and separate vessels
which are located such that a highly hazardous chemical
could be involved in a potential release shall be considered
a single process”; correct?
A. Yes, ma’am.
Q. And since the term “vessel” isn’t defined in the standard,
can you tell us what you interpret the term “vessel” to
mean?
A. A vessel can be a container. It can also be in some
instances a pressure vessel, but for the most part a
container.
Q. I’m sorry?
A. For the most part, a container.
Q. Would it need to contain an HHC or flammable?
Process Safety Management of Highly Hazardous Chemicals—Compliance
Guidelines and Enforcement Procedures, Occupational Safety & Health
Administration (Sept. 28, 1992), https://www.osha.gov/enforcement/
directives/cpl-02-02-045.
12
A. Yes, I believe so. Yes.
R., vol. I, at 1234 (emphasis added). Given this concession by its
designated representative, I would reject the Secretary’s current argument
that the second sentence could apply even if the interconnected or nearby
vessel contains no HHC.
G. Though the first sentence could apply even when the vessel
contains no HHC, the Commission has not relied on the first
sentence.
The Secretary argues that other provisions of the PSM standard show
“that the presence of a HHC in a vessel is not a precondition to coverage.”
Secretary’s Resp. & Opening Br. at 39. The Secretary is right, but only
under the “process” definition’s first sentence (when a vessel is used in an
activity involving a covered process). See Oral Arg. at 43:58–46:37
(responding to a hypothetical and explaining that vessels without HHCs
could be considered process equipment depending on their use); see also
Process Safety Management of Highly Hazardous Chemicals—Compliance
Guidelines and Enforcement Procedures, Occupational Safety & Health
Administration (Sept. 28, 1992), https://www.osha.gov/enforcement/
directives/cpl-02-02-045 (“Furnaces, boilers, heaters, etc., fueled by
flammable liquids or gases--regardless of the quantity of the fuel--used in
processes that are otherwise covered by the PSM standard . . . are
considered part of the process and are covered by the PSM standard.”).
Here, though, the Secretary and Commission relied on the “process”
13
definition’s second sentence, which considers the boiler’s interconnection
or proximity to a covered process, not the boiler’s use in a process
activity. For coverage under the second sentence, the presence of an HHC
is required to trigger the PSM standard.
* * *
Because the boiler did not contain any HHC, I would reverse the
Commission’s determination of PSM coverage as to the eleven citations
involving the boiler.
II. The Commission committed legal error in applying the test of
substantial continuity.
The Secretary characterized five of Wynnewood’s twelve citations as
repeat violations, which triggered heightened penalties. See 29 U.S.C.
§ 666(a) (providing heightened penalties against employers who commit
repeated violations). The Secretary based this characterization on
violations committed by Wynnewood’s predecessor. But the Commission
determined that Wynnewood is not a successor and rejected the Secretary’s
characterization of Wynnewood as the same entity cited for previous
violations.
The majority concludes that the Commission did not err. I
respectfully disagree and would remand for further consideration of
heightened penalties for the single “repeat” citation not involving the
boiler.
14
A. We review the Commission’s factual findings for substantial
evidence and legal conclusions for conformity with the law.
When reviewing the Commission’s decision, we examine factual
determinations under the substantial-evidence standard. 29 U.S.C.
§ 660(a); see Slingluff v. OSHRC, 425 F.3d 861, 866 (10th Cir. 2005)
(“[F]indings of the Commission with respect to questions of fact, if
supported by substantial evidence on the record . . . shall be conclusive.”
(quoting Interstate Erectors, Inc. v. OSHRC, 74 F.3d 223, 226 (10th Cir.
1996))). We also set aside the Commission’s legal conclusions if they are
“not in accordance with law.” 5 U.S.C. § 706(2)(A).
To determine whether a predecessor’s violations may be attributed to
a successor, the Commission applies a three-factor test involving
“substantial continuity.” See Sharon & Walter Constr., Inc., 23 BNA
OSHC 1286 (No. 00-1402, 2010), 2010 WL 4792625 at *9 (focusing on
“whether there is ‘substantial continuity’ between the two enterprises”
(quoting Fall River Dyeing & Finishing Corp. v. NLRB, 482 U.S. 27, 43
(1987))).
The Secretary argues that the Commission
improperly treated the absence of one of the three factors as
automatically dispositive and
misapplied that factor.
15
Responding to this argument, Wynnewood urges application of the
substantial-evidence standard on the ground that the test of substantial
continuity turns on factual determinations.
Wynnewood has misinterpreted the Secretary’s arguments. The
Secretary argues that the Commission misapplied its own precedents, not
that the Commission erred in its factual findings. Given the Secretary’s
argument, the majority correctly concludes that we apply de novo review.
Majority Op. at 17; see Mountain Side Mobile Estates P’ship v. Sec’y of
Hous. & Urban Dev., 56 F.3d 1243, 1250 (10th Cir. 1995) (stating that our
review is not deferential on legal questions, such as whether the agency
applied the correct legal standard).
B. The Commission considers substantial continuity based on
three factors.
The Commission applied the “substantial-continuity test” for
successorship in Sharon & Walter, adapting the test used in labor-relations
cases. 23 BNA OSHC 1286 (No. 00-1402, 2010), 2010 WL 4792625. The
substantial-continuity test evaluates “the totality of the circumstances,”
focusing “on whether the new [entity] has ‘acquired substantial assets of
its predecessor and continued, without interruption or substantial change,
the predecessor’s business operations.’” Coastal Derby Ref. Co. v. NLRB,
915 F.2d 1448, 1452 (10th Cir. 1990) (quoting Fall River Dyeing &
Finishing Corp. v. NLRB, 482 U.S. 27, 43 (1987)). When applying that
16
standard to violations of the Occupational Safety and Health Act, the
Commission considers three factors:
1. the nature of the business, with continuity in the nature of the
business indicating a lack of substantive change in the
enterprise,
2. the continuity in the jobs and working conditions, which are
correlated with safety and health hazards, and
3. the continuity of safety and health personnel.
Sharon & Walter, 23 BNA OSHC 1286, 2010 WL 4792625 at *10.
C. The Commission improperly treated the third factor as
automatically dispositive.
As the Secretary argues, the Commission improperly treated the final
factor (continuity of personnel) as a required element of substantial
continuity.
The Commission found that
the first two factors of the test support a finding of substantial
continuity and
the third factor cuts against a finding of substantial continuity.
See Commission’s Order at 13 (“[T]he refinery’s business, products, jobs,
and working conditions were the same under both entities.”); id. at 15
(“[T]he record does not support the Secretary’s contention that there
was . . . continuity in the safety personnel . . . .”). After making these
factual findings, the Commission treated the absence of the third factor as
automatically dispositive.
17
The Commission can use discretion in balancing the three factors.
But in exercising that discretion, the Commission treated the absence of
the third factor as automatically fatal to the Secretary’s argument on
substantial continuity. The Commission erred because the absence of any
single factor is not automatically fatal to substantial continuity. See Haw.
Carpenters Trust Funds v. Waiola Carpenter Shop, Inc., 823 F.2d 289, 294
(9th Cir. 1987) (stating that the absence of one factor in a similar test does
not prevent characterization as the same entity); see also Ind. Elec.
Workers Pension Benefit Fund v. Manweb Servs., Inc., 884 F.3d 770, 783
(7th Cir. 2018) (stating that “[t]he presence or absence of any one factor
‘does not compel a particular conclusion’” on successor liability) (quoting
Resilient Floor Covering Pension Tr. Fund Bd. of Trs. v. Michael’s Floor
Covering, Inc., 801 F.3d 1079, 1091 (9th Cir. 2015)).
The Commission could conclude that one factor outweighed the other
two factors. But the Commission didn’t do that. The Commission instead
concluded that the failure to satisfy the third factor would necessarily
prevent consideration of Wynnewood as a successor: “[W]e agree that the
last prong of the three-part ‘substantial continuity’ test . . . was not met in
this case—and that [the two companies] are therefore not the same
employer for repeat characterization purposes under Sharon & Walter
. . . .” Commission’s Order at 15 n.14; see also id. at 15 (“[T]he record
does not support the Secretary’s contention that there was sufficient
18
continuity in the safety personnel at the cited entity such that ‘there was a
Commission final order against the same employer for a substantially
similar violation.’” (emphasis in original) (citation omitted)).
The majority says that the Commission “never indicat[ed] that the
test required continuity across all three factors.” Majority Op. at 17. But
the Commission expressly found that the employer was not the same
because of the Secretary’s failure to satisfy the third factor. In doing so,
the Commission treated the third part of the test as a necessary element
rather than as a factor.
Wynnewood defends the Commission’s reliance on the third factor,
arguing that it is the most important of the three. For this argument,
Wynnewood points to Sharon & Walter, explaining that continuity of
“control over decision-making in both companies . . . weighs heavily in
favor of” finding substantial continuity. 23 BNA OSHC 1286, 2010 WL
4792625 at *10. But Sharon & Walter explained the importance of the third
factor in the context of the facts in that case. The third factor “weigh[ed]
heavily” there because the same person had owned both the old and new
entities. But Sharon & Walter didn’t suggest that the third factor would
always outweigh the other factors.
After finding that the third factor cut against a repeat
characterization, the Commission needed to explain why that factor
outweighed the other two. The majority says that “the Commission
19
explained how the change in personnel directly impacted the safety of the
refinery, demonstrating why it weighed that factor so heavily.” Majority
Op. at 17–18. But the Commission never explained why the third factor
would override the other two. The Commission said only that “the record
does not support the Secretary’s contention that there was sufficient
continuity in the safety personnel” supporting a repeat violation and
“[a]ccordingly, we find that a repeat characterization is not warranted
here.” Commission’s Order at 15–16. The Commission’s language shows
that it treated the absence of the third factor as automatically fatal to
characterization of the violations as “repeat.”
The Commission’s failure to properly weigh the three factors
constitutes a legal error.
D. The Commission also misapplied the third factor.
The Commission also improperly applied the third factor.
The Commission framed its analysis of the third factor by
considering
a shift in policies and workplace culture after Wynnewood’s
acquisition and
Wynnewood’s lack of intent to manipulate the successorship
doctrine.
But these reasons should not affect consideration of the third factor.
20
1. A shift in policies and workplace culture does not bear on
the third factor.
The Commission relied in part on the change in safety policies and
culture at Wynnewood after the acquisition. See Commission’s Order at 14
(“These leadership changes resulted in a safety culture shift at the refinery.
In light of the foregoing, we find these are not the appropriate
circumstances to affirm a repeat characterization.”) (footnote omitted); id.
at 14 n.13 (“[W]e conclude that Wynnewood LLC’s changeover in
ownership resulted in changes in management practices, procedures, and
culture significant enough to break the chain of liability . . . .”). For the
sake of argument, we may assume that the Commission could consider
these changes under the test for substantial continuity. Even so, those
changes would not affect the third factor, which Wynnewood and the
majority characterize as the most important of the three factors.
The third factor doesn’t consider whether the employees of the new
entity acted differently than they had in the past. This factor instead
focuses on whether the employees addressing safety were the same in both
the old and new entities. See Sharon & Walter, 23 BNA OSHC 1286, 2010
WL 4792625 at *10 (examining the continuity of personnel who had
“control over decision-making,” but not the continuity of those decisions).
The Commission’s focus undermines the purpose of inquiring into
whether the old and new entities are the same. This inquiry matters
21
because once an entity has been cited, the citation “tends to apprise the
[entity] of the requirements of the standard and to alert [it] that special
attention may be required to prevent future violations of that standard.”
Dun-Par Eng’d Form Co. v. Marshall, 676 F.2d 1333, 1337 (10th Cir.
1982). A repeat violation does not depend on a showing of intent and
cannot be cured by the entity’s change in policy.
A policy change could conceivably weigh against a finding of
willfulness. See Sharon & Walter, 23 BNA OSHC 1286, 2010 WL 4792625
at *5 (“The hallmark of a willful violation is the employer’s state of mind
at the time of the violation-an ‘intentional, knowing, or voluntary
disregard for the requirements of the Act or . . . plain indifference to
employee safety.’” (citation omitted)). But willfulness constitutes a
separate basis for heightened penalties. See 29 U.S.C. § 666(a) (“Any
employer who willfully or repeatedly violates the requirements . . . may be
assessed a civil penalty . . . .”). The Commission improperly conflated the
inquiries for substantial continuity and willfulness.
2. The third factor does not address the entity’s possible
manipulation.
The Commission also erred by relying on Wynnewood’s lack of
manipulation.
In applying the third factor, the Commission noted: “This is not a
case where ‘the cited employer has altered its legal identity from that of
22
the predecessor employer . . . [simply to] avoid a repeat characterization.’”
Commission’s Order at 14–15 (quoting Sharon & Walter, 23 BNA OSHC
1286, 2010 WL 4792625 at *8) (alterations in original). The Commission
also explained that it “s[aw] no rationale here for imposing the OSHA
violation history of Wynnewood Inc. upon Wynnewood LLC, a separate
legal entity not created to avoid responsibilities under the Act.” Id. at 15
n.14. By focusing on a lack of manipulation, the Commission improperly
conflated the substantial-continuity test and the alter-ego test.
The majority recognizes that the substantial-continuity test does not
focus on whether a new entity was intended as a sham. See Majority Op. at
19. And Wynnewood admits that the Commission’s formulation of the
substantial-continuity test serves as the functional equivalent of the alter-
ego test. See Wynnewood’s Resp. & Reply Br. at 10 (“[The Commission’s]
substantial continuity test . . . looks for overlap more akin to an alter ego,
and especially for evidence of a sham transition . . . .”); Oral Arg. at
50:00–50:10 (“The primary purpose of [the Commission’s] successorship
test is to defeat those kinds of efforts by employers to purposefully evade
repeat liability by engaging in sham transactions.”). But the tests for alter
ego and substantial continuity differ. Given this difference, the
23
Commission didn’t just use the wrong label; the Commission mistakenly
conflated the two tests. 5
The majority discounts the Commission’s discussion of
Wynnewood’s motive, calling the discussion “dicta” and assuming that the
discussion wasn’t essential to the decision. Majority Op. at 19. How does
the majority know that the Commission didn’t rely on its discussion of
Wynnewood’s motive? Labelling the discussion “dicta” might affect the
discussion’s status as precedent, but doesn’t explain whether the erroneous
discussion tainted the Commission’s findings on the third factor.
C. The appropriate remedy is remand.
The Secretary suggests that if we conclude that the Commission had
committed legal error, we should conduct our own factual analysis of the
substantial-continuity test. But even if we were to agree with the
Secretary’s factual analysis, a remand would remain necessary for the
Commission to determine whether the cited violations are substantially
similar to the prior violations. See Potlatch Corp., 7 BNA OSHC 1061 (No.
16183, 1979), 1979 WL 61360 at *3 (“A violation is repeated . . . if . . .
there was a Commission final order against the same employer for a
5
Wynnewood contends that the successorship doctrine should not
discourage mobility of capital. Wynnewood’s Resp. & Reply Br. at 24–26.
But Wynnewood doesn’t explain how mobility of capital should affect our
analysis of the third factor.
24
substantially similar violation.”). Given the factual nature of this inquiry, I
would remand to the Commission to reconsider its application of the
substantial-continuity test.
III. Conclusion
In my view, the PSM standard applies to interconnected or nearby
vessels only when each vessel contains an HHC. Because the boiler didn’t
contain any HHC, I would vacate the eleven citations involving the boiler.
I would also conclude that the Commission improperly applied the
substantial-continuity test, so I would remand for the Commission to
reconsider heightened penalties for the single repeat violation not
involving the boiler. I thus respectfully dissent.